TABLE 17

High Heat

Unit

 

CO2% For Nat

CO2% For L.P.

G61MP−36B−045

 

6.5 − 7.5

7.4 − 8.4

 

 

 

 

G61MP−36B−070

 

6.5 − 7.5

7.4 − 8.4

 

 

 

 

G61MP−48C−090

 

6.9 − 7.9

7.8 − 8.8

 

 

 

 

G61MP−60C−090

 

6.9 − 7.9

7.8 − 8.8

 

 

 

 

G61MP−48C−110

 

7.2 − 8.2

8.1 − 9.1

 

 

 

 

G61MP−60C−110

 

7.2 − 8.2

8.1 − 9.1

 

 

 

 

G61MP−60D−135

 

7.4 − 8.4

8.3 − 9.3

 

 

 

 

 

TABLE 18

 

 

Low Heat

 

Unit

 

CO2% For Nat

CO2% For L.P.

G61MP−36B−045

 

4.8 − 5.8

5.3 − 6.3

 

 

 

 

G61MP−36B−070

 

4.8 − 5.8

5.3 − 6.3

 

 

 

 

G61MP−48C−090

 

5.1 − 6.1

5.9 − 6.9

 

 

 

 

G61MP−60C−090

 

5.1 − 6.1

5.9 − 6.9

 

 

 

 

G61MP−48C−110

 

5.3 − 6.3

6.1 − 7.1

 

 

 

 

G61MP−60C−110

 

5.3 − 6.3

6.1 − 7.1

 

 

 

 

G61MP−60D−135

 

5.7 − 6.7

6.7 − 7.7

 

 

 

 

H− High Altitude

NOTE − In Canada, certification for installations at eleva- tions over 4500 feet (1372 m) is the jurisdiction of local au- thorities.

The manifold pressure may require adjustment to ensure proper operation at higher altitudes. Refer to table 19 for proper manifold pressure settings at varying altitudes and required pressure switch changes and conversion kits at varying altitudes.

The combustion air pressure switches are factory−set and require no adjustment.

NOTE − A natural to L.P. propane gas changeover kit is nec- essary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

I− Condensate pH Range

The condensate is mildly acidic and can be measured with pH indicators. The pH scale is a measurement of acidity and alkalinity. The following scale shows the relative pH of some common liquids as compared with condensate of G61MP units. The concentration of the acidity of all these fluids including the condensate is very low and harmless.

pH RANGE

 

0

 

 

 

 

1

 

 

 

Increasing 2

 

Vinegar

G61 Condensate

 

Acidity

3

 

Wine

 

4

 

Orange Juice

pH Range

 

 

 

 

5Tomato Juice

6

7 Tap Water

8

Increasing 9

Alkalinity 10

11

TABLE 19

Conversion Kit Requirements and Manifold Pressures

 

 

 

 

Altitude

 

 

Manifold Pressure at all

 

 

 

 

 

 

 

altitudes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

0−4500 ft.

4501−7500 ft.

7501−10,000

Low Fire

High Fire

Input

Gas

(0−1372 m)

(1373−2286 m)

(2287−3048 m)

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

Required

Pressure

Required

Pressure

Required

Pressure

in.

 

in.

 

 

 

 

 

 

 

Conversion

Conversion

Conversion

kPa

kPa

 

 

Switch

Switch

Switch

w.c.

w.c.

 

 

Kit

Kit

Kit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nat

N/A

No Change

N/A

No Change

59M16

No Change

1.7

0.42

3.5

0.87

−045

 

 

 

 

 

 

 

 

 

 

 

 

LPG

59M13

No Change

59M13

No Change

59M14

No Change

4.9

1.22

10.0

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Nat

N/A

No Change

N/A

No Change

59M16

56M06

1.7

0.42

3.5

0.87

−070

 

 

 

 

 

 

 

 

 

 

 

 

LPG

59M13

No Change

59M13

No Change

59M14

56M06

4.9

1.22

10.0

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Nat

N/A

No Change

N/A

75M22

59M16

56M21

1.7

0.42

3.5

0.87

−090

 

 

 

 

 

 

 

 

 

 

 

 

LPG

59M13

No Change

59M13

75M22

59M14

56M21

4.9

1.22

10.0

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Nat

N/A

No Change

N/A

No Change

59M16

No Change

1.7

0.42

3.5

0.87

−110

 

 

 

 

 

 

 

 

 

 

 

 

LPG

59M13

No Change

59M13

No Change

59M14

No Change

4.9

1.22

10.0

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Nat

N/A

No Change

N/A

59M93

59M16

56M93

1.7

0.42

3.5

0.87

−135

 

 

 

 

 

 

 

 

 

 

 

 

LPG

59M13

No Change

59M13

59M93

59M14

56M93

4.9

1.22

10.0

2.5

 

 

 

 

 

 

 

 

 

 

 

 

Pressure switch is factory set. No adjustment necessary. All models use the factory installed pressure switch from 0−4500 feet (0−1370 m).