Lennox International Inc G61MP specifications Venting Practices

Models: G61MP

1 54
Download 54 pages 6.93 Kb
Page 19
Image 19
STRAPPING (metal, plastic or large wire ties)
FIGURE 12

C− Venting Practices

The thickness of construction through which vent pipes may be installed is 24" (610mm) maximum and 3" (76mm) minimum. If a G61MP furnace replaces a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue prod- ucts, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.

1.Use recommended piping materials for exhaust pip- ing.

2.Secure all joints so that they are gas-tight using ap- proved cement.

Suspend piping using hangers at a minimum of every 5 feet (1.52m) for schedule

40 PVC and every 3 feet

(.91m) for ABS−DWV, PVC− DWV, SPR−21 PVC, and SDR−26 PVC piping. A suit- able hanger can be fabri- cated by using metal or plastic strapping or a large wire tie.

3.In areas where piping penetrates joists or interior walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.

4.Isolate piping at the point where it exits the outside wall or roof in order to prevent transmission of vibration to the structure.

5.When furnace is installed in a residence where unit is shut down for an extended period of time, such as a vacation home, make provisions for draining conden- sate collection trap and lines.

Exhaust Piping

NOTE − A 2" diameter street ell is strapped to the blower deck of 48C−110 and 60C−110 units. Street ell must be glued directly into the unit flue collar. See figure 13. A 3" to 2" reducing ell is strapped to the blower deck of the 60D−135 units. In upflow or downflow applications, the reducing ell must be glued directly into the unit flue collar.

1.Choose the appropriate side for venting in upflow or downflow positions. Exhaust piping exits from the top of the unit in horizontal air discharge applications. Glue the field−provided exhaust vent pipe (or provided street ell or reducing ell in upflow or downflow applica- tions) to the flue collar. All cement joints should be made according to the specifications outlined in ASTM D 2855. Refer to pipe and fittings specifications and gluing procedures.

TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION

IN UPFLOW OR DOWNFLOW DIRECT OR NON-DIRECT VENT APPLICATIONS

(Right-Hand Exit in Upflow Application Shown)

PLUG

PLUG

2”

VENT PLUG

2”

2"

 

(Must be

 

 

glued in

 

 

place)

 

 

PLUG

 

 

 

CONDENSATE

 

 

TRAP

 

 

(Must be installed

 

on same side as

 

exhaust piping)

 

*2" diameter street elbow provided. **3" diameter reducing elbow provided.

***Limit pipe length to 2".

2−1/2", 3", OR 4"

 

 

 

 

 

 

 

 

 

 

 

 

 

REDUCER

 

 

 

 

 

 

 

G61MP−045, 070

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or 090 with 2−1/2",

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2”

 

 

 

 

 

3", or 4" vent pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2”

4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2−1/2",

2”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REDUCER

 

 

 

 

 

3", OR

 

 

 

 

 

 

 

 

 

 

 

(use only if

 

 

 

 

 

4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4" pipe is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

required)

 

 

 

 

 

 

 

 

REDUCER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2"***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2"*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3"**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G61MP−110 with

 

 

 

 

 

 

 

 

 

G61MP−135 with

2−1/2", 3", OR 4"

 

 

 

 

 

 

 

3" OR 4" vent pipe

 

 

vent pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 13

Page 19

Page 19
Image 19
Lennox International Inc G61MP specifications Venting Practices, Upflow or Downflow Direct or NON-DIRECT Vent Applications