![Installation](/images/new-backgrounds/35469/354697x1.webp)
If a return air plenum is used, the return air grille should be immediately in front of the opening in the plenum to allow for the free flow of return air. When not installed in front of the opening, there must be adequate clearance around the air handler to allow for the free flow of return air.
Installation
Each unit consists of a blower assembly, refrigerant coil, and controls, in an insulated galvanized steel factory finished enclosure. Knockouts are provided for electrical wiring entrance.
For ease in installation, it is best to make any necessary coil configuration changes before setting air handler in place.
REFRIGERANT METERING DEVICE
CB25UH units are equipped with a
UPFLOW APPLICATION
1.The air handler must be supported on the bottom only and set on solid floor or field‐supplied support frame. Securely attach the air handler to the floor or support frame.
2.If installing a unit in an upflow application, remove the
horizontal drain pan. IMPORTANT - The horizontal drain pan is not required in upflow air discharge installations; its removal provides the best efficiency and air flow.
3.Place the unit in the desired location and slope unit as previously mentioned. Connect return and supply air plenums as required using sheet metal screws.
4.Install units that have no return air plenum on a stand that is at least 14” from the floor. This will allow proper air return.
HORIZONTAL APPLICATIONS
IMPORTANT
When removing the coil, there is possible danger of equipment damage and personal injury. Be careful when removing the coil assembly from a unit installed in right- or
ANGLE IRON OR SHEET | ELECTRICAL INLET CLEAR |
METAL MAXIMUM 1/2” | ANCE 4 IN. (102 MM) |
LONG SCREW |
|
AIR FLOW |
|
FRONT VIEW | END VIEW |
Figure 2. Suspending Horizontal Unit
NOTE — When the unit is installed in horizontal applications, a secondary drain pan is recommended. Refer to local codes.
NOTE — This unit may be installed in
LEFT-HAND DISCHARGE
HORIZONTAL DRAIN PAN
IMPORTANT! REMOVE PAN
FOR BEST EFFICIENCY
AND AIR FLOW.
UPFLOW
DRAIN PAN
UPFLOW DRAIN CON
NECTIONS (BOTH
SIDES; USE ONE SIDE
OR OTHER)
HORIZONTAL DRAIN CONNECTIONS (BOTH SIDES; NOT USED)
1.Determine knockouts required for drain line connections.
2.With access door removed, knock out drain line opening for installing drain lines.
3.Set unit so that it is sloped toward the drain pan end of the unit (see figure 10).
4.The horizontal configuration is shown in figure 3.
AIR FLOW
Drains
KNOCKOUT | LEFT‐HAND DRAINS |
Figure 1. Upflow Configuration
Figure 3. Left‐Hand Discharge Configuration
Page 4