Lennox International Inc Lennox Air Handler Condensate Drain, Blow-OffPrevention Plate, Vent

Models: Merit CBX25UH Series Lennox Air Handler

1 16
Download 16 pages 901 b
Page 6
Image 6
Figure 8. Blow-Off Prevention Plate

HORIZONTAL RIGHT

HORIZONTAL LEFT

 

REMOVE 2 SCREWS

(FACTORY DEFAULT)

 

SECURING BLOW OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PREVENTION BRACKET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROTATE BRACKET TO THIS

POSITION AND REINSTALL

Figure 8. Blow-Off Prevention Plate

Condensate Drain

Condensate DrainIMPORTANT

On units of this type, where the blower “draws” rather than “blows” air through the coil, traps must be installed in the con­ densate drain lines (primary and auxiliary, if used). Traps prevent the blower from drawing air through the drain lines into the air supply.

ABOVE

FINISHED

SPACE?

NO

OVERFLOW DRAIN LINE

ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO ROUTE OVERFLOW DRAIN LINE, INSTALL LOW VOLTAGE OVERFLOW SWITCH KIT. WIRE KIT TO SHUT DOWN COMPRESSOR PER INSTRUCTIONS.

LENNOX #

X3169

COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET AND MALE ADAPTER, TWO PART DESIGN FOR USE WHERE OBSTRUCTIONS PREVENT DIRECT THREADING

 

VENT MUST EXTEND

 

 

 

ABOVE HEIGHT OF

 

 

 

COIL DRAIN PAN BY

 

 

TWO INCHES (51MM)

VENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CLEAN OUT

 

 

 

PRESS IN

 

 

(DO NOT GLUE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR HANDLER DRAIN PAN

MAIN

1” X 3/4” X 3/4”

 

DRAIN

REDUCING

OVERFLOW

 

TEE WITH

 

PLUG

DRAIN

 

 

 

YES

NOTE — WHEN A AIR HANDLER IS LOCATED ABOVE A FINISHED SPACE THE SECONDARY DRAIN PAN MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER.

SECONDARY

DRAIN PAN

WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A 3/4” (19.1MM) SECONDARY DRAIN LINE MUST BE:

SCONNECTED TO SECONDARY DRAIN PAN OR

SCONNECTED TO THE OVERFLOW DRAIN OUTLET OF THE AIR HANDLER DRAIN PAN.

LENNOX1 P-TRAP

49P66, J-TRAP #

91P90 OR ANY

PVC SCH 40 P- OR

J-TRAP 3/4”2” (51MM)

TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES — GENERALLY, TWO INCHES (51MM).

1LENNOX P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.

2PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4” I. D. X 5” - 34K7401 (1): CUT THE PIPE IN HALF AND USE IT TO ROUTE THE MAIN DRAIN.

TRAP DEPTH

TO APPROVED

 

 

DRAIN

 

FOR NEGATIVE PRESSURE COILS (BLOWER

DRAIN LINE SHOULD

AFTER COIL) TRAPS ARE REQUIRED ON ALL

SLOPE A MINIMUM OF

DRAIN LINES CONNECTED TO COIL.

ONE

INCH

PER

10

 

 

FEET

(25MM

PER

3

 

METERS)

 

 

Figure 9. Typical Main and Overflow Drain

Page 6

Page 6
Image 6
Lennox International Inc Lennox Air Handler Condensate Drain, Blow-OffPrevention Plate, Typical Main and Overflow Drain