Lennox International Inc 506945-01 Indoor Expansion Valve Installation, Uncased Coil Shown

Models: 506945-01 Merit Series Air Conditioner

1 15
Download 15 pages 63.32 Kb
Page 8
Image 8
INDOOR EXPANSION VALVE INSTALLATION

STEP 2 -- REFRIGERANT PIPING -- Installing Indoor Expansion Valve

This outdoor unit is designed for use in systems that use either an fixed orifice (RFC) (included with outdoor unit), or expansion valve metering device (purchased separately) at the indoor coil. See the 13ACX Product Specifications bulletin (EHB) for approved expansion valve kit match ups. The expansion valve unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the expansion valve in a manner that will provide access for field servicing of the expansion valve. Refer to below illustration for reference during installation of expansion valve unit. After installation of the indoor coil metering device, proceed to Step 5.

INDOOR EXPANSION VALVE INSTALLATION

TWO-PIECE

 

(Uncased Coil Shown)

 

PATCH PLATE

 

 

(UNCASED

 

 

 

STUB

 

 

COIL ONLY)

LIQUID LINE

 

 

END

 

 

 

 

ORIFICE

 

EXPANSION

 

 

 

 

 

 

 

 

HOUSING

 

 

DISTRIBUTOR

 

 

VALVE

 

 

 

 

 

 

 

 

 

 

 

 

TUBES

 

 

 

 

 

TEFLON®

 

 

 

 

 

 

 

 

 

 

 

 

RING

 

 

 

 

TEFLON®

SENSING

 

 

 

 

RING

 

 

 

 

 

 

LINE

 

 

 

 

 

 

DISTRIBUTOR

 

EQUALIZER

 

ASSEMBLY

 

 

LINE

 

 

 

 

 

 

 

LIQUID LINE

 

 

 

 

 

ASSEMBLY WITH

CInstall one of the provided Teflon® rings around the stubbed end of the expansion valve and use refrigerant

oil to lightly lubricate the connector threads and ex­ posed surface of the Teflon® ring.

DAttach the stubbed end of the expansion valve to the liquid line orifice housing. Finger tighten, then use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure to the right, or tighten to 20 ft-lb.

EPlace the remaining Teflon® washer around the other

end of the expansion valve. Lightly lubricate connector threads and expose surface of the Teflon® ring with refrigerant oil.

FAttach the liquid line assembly to the expansion valve. Finger tighten, then use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or tighten to 20 ft-lb.

1/2 Turn

11 12

1

10

 

2

9

 

43

8 7

6

5

 

 

BRASS NUT

MALE EQUALIZER LINE

VAPOR

 

FITTING (SEE

 

LINE

 

EQUALIZER LINE

 

 

 

INSTALLATION FOR

 

 

DETAILS)

 

 

Sensing bulb insulation is required if

 

expansion valve is installed external to the

LIQUID LINE

coil casing. See sensing bulb installation for

 

bulb positioning.

 

 

SENSING BULB INSTALLATION

AAttach the vapor line sensing bulb in the proper orienta­ tion as illustrated below using the clamp and screws provided.

BNOTE - Though it is preferred to have the sensing bulb installed on a horizontal run of the vapor line, installation on a vertical run of piping is acceptable if necessary.

NOTE — Confirm proper thermal contact between vapor line and expansion bulb before insulating the sensing bulb.

CConnect the equalizer line from the expansion valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut, then tighten an additional 1/8 turn (7 ft-lbs) as illustrated to the right.

 

1/8 Turn

 

11 12

1

10

 

2

9

 

 

43

8

7

6

5

EQUALIZER LINE INSTALLATION

ARemove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure below.

BRemove the field-provided fitting that temporarily reconnected the liquid line to the indoor unit's distributor assembly.

FLARE SEAL CAP

 

FLARE NUT

 

OR

COPPER FLARE

 

SEAL BONNET

 

 

 

 

MALE BRASS EQUALIZER

 

 

LINE FITTING

 

 

VAPOR LINE

VAPOR LINE

12

BULB

VAPOR LINE

12

BULB

ON LINES SMALLER THAN 7/8”, MOUNT SENSING BULB AT EITHER THE 3 OR 9 O'CLOCK POSITION.

BULB

ON 7/8” AND LARGER LINES,

MOUNT SENSING BULB AT

EITHER THE 4 OR 8 O'CLOCK

POSITION. NEVER MOUNT

THE SENSING BULB ON

BOTTOM OF LINE.

BULB

NOTE — NEVER MOUNT THE SENSING

BULB ON BOTTOM OF LINE.

FIGURE 10

Page 8

Page 8
Image 8
Lennox International Inc 506945-01 Indoor Expansion Valve Installation, Uncased Coil Shown, Sensing Bulb Installation