Lennox International Inc Merit Series Gas Furnace Continuous Heat Speed Fan Sequence Of Operation

Models: Merit Series Gas Furnace

1 43
Download 43 pages 49.12 Kb
Page 43
Image 43
CONTINUOUS HEAT SPEED FAN SEQUENCE OF OPERATION

Troubleshooting: Continuous Fan Sequence of Operation

CONTINUOUS HEAT SPEED FAN SEQUENCE OF OPERATION

LED: SLOW FLASH RATE REMAINS

UNCHANGED THROUGHOUT SEQUENCE.

MANUAL FAN SELECTION MADE AT THERMOSTAT. CONTROL (G) ENERGIZES SYSTEM FAN AT HEAT SPEED. EAC TERMINAL IS ENERGIZED.

THERMOSTAT CALLS FOR HEAT (W).

NOYES

HUM TERM. ENERGIZES WITH COMB. AIR INDUCER.

THERMOSTAT CALLS FOR COOLING.

YES

NO

 

SYSTEM FAN SWITCHED TO COOL SPEED.

EAC TERM. REMAINS ON.

THERMOSTAT OPENS.

MANUAL FAN SELECTION MADE AT THERMOSTAT. Manual backgroundManual background CONTROL (G) ENERGIZES SYSTEM FAN AT HEAT

SPEED. EAC TERM. ENERGIZED.

SYSTEM FAN REMAINS ON

HEATING SPEED.

THERMOSTAT OPENS.

HUM TERM. DE−ENERGIZES WITH COMB. AIR INDUCER

SYSTEM FAN REMAINS ON

HEATING SPEED.

Page 43

Page 43
Image 43
Lennox International Inc Merit Series Gas Furnace installation instructions Continuous Heat Speed Fan Sequence Of Operation