Integrated Control Diagnostic Codes

Integrated Control Diagnostic Codes

DIAGNOSTIC CODES

Make sure to Identify LED’S Correctly.

LED #1 (Red)

LED #2 (Green)

DESCRIPTION

SIMULTANEOUS

SIMULTANEOUS

Power on − Normal operation.

SLOW FLASH

SLOW FLASH

Also signaled during cooling and continuous fan.

 

 

 

SIMULTANEOUS

SIMULTANEOUS

Normal operation − signaled when heating demand initiated at thermostat.

FAST FLASH

FAST FLASH

 

 

 

 

SLOW FLASH

ON

Primary or secondary limit switch open. Limit must close within 3 minutes or unit

goes into 1 hour Watchguard.

 

 

 

 

 

 

 

Pressure prove switch open.

OFF

SLOW FLASH

OR: Blocked inlet/exhaust vent;

 

 

OR: Pressure switch closed prior to activation of combustion air inducer.

 

 

 

ALTERNATING

ALTERNATING

Watchguard 1 hour − burners failed to ignite or lost flame 5 times during single

SLOW FLASH

SLOW FLASH

heating demand.

 

 

 

SLOW FLASH

OFF

Flame sensed without gas valve energized.

 

 

 

ON

SLOW FLASH

Rollout switch open. OR: 12-pin connector improperly attached.

 

 

 

ON

ON

 

ON

OFF

Circuit board failure or control wired incorrectly.

OFF

ON

 

 

 

 

FAST FLASH

SLOW FLASH

Main power polarity reversed. Switch line and neutral.

 

 

 

SLOW FLASH

FAST FLASH

Low flame signal. Measures below 1.5 microamps. Replace flame sense rod.

 

 

 

ALTERNATING

ALTERNATING

Improper main ground.

FAST FLASH

FAST FLASH

OR: Line voltage below 90 volts.

 

 

 

NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second). Minimum flame sense current = 0.5 microAmps.