| Burner Blower Motor | Visually check to see if motor is running. If not, |
|
| check for 120 VAC to motor at motor connector (wire |
|
| #5 and #22). If voltage is not present, trace wiring |
|
| back to fan switch. If voltage is present and motor is |
|
| not running, check for opens, shorts, or grounds. |
|
| Also, WITH POWER OFF: check for locked rotor. |
| Transformer, Burner | Primary is 120 VAC with 24 VAC secondary. If 120 |
|
| VAC is not present, trace wiring back to Main Fan |
|
| Centrifugal Switch. If 120 VAC is present, check for |
|
| 24 VAC at secondary of transformer. If no voltage is |
|
| present, replace transformer. |
| Centrifugal Switch of Burner | Check of 120 VAC at motor connector, on wire #13 |
| Blower Motor | to neutral. If voltage is not present, trace wiring back |
|
| to transformer. If voltage is not present and motor is |
|
| running, replace the burner blower motor. |
| Ignition Control | 24 volts should be present at 24 volt terminals. If not |
|
| present, trace wiring back to centrifugal switch. |
|
| When 24 VAC is supplied, the control switches 120 |
|
| VAC from L1 and L2 to the hot surface ignitor. if 120 |
|
| VAC is not present at L1 and L2, trace wiring |
|
| back to fan switch. If 24 VAC and 120 VAC are |
|
| present and 120 VAC is not across the hot surface |
|
| ignitor terminals, replace the ignition control. |
| Hot Surface Ignitor | If 120 VAC is present at hot surface ignitor terminals, |
|
| visually check to see that the ignitor is heating. |
|
| (Ignitor may be viewed through the port glass in end |
|
| of burner tube.) The ignitor should glow bright red. |
|
| If the ignitor does not heat, replace the ignitor. |
| Ignition Control | After 45 seconds of hot surface ignitor |
|
| ignition control will switch 24 VAC to the gas control |
|
| valves. Check for 24 VAC output from ignition |
|
| control, across terminals marked "valve" and "valve |
|
| ground". If no voltage is present, replace ignition |
|
| control. |
| Gas Control Valves | When 24 VAC is supplied to the gas control valve, |
|
| the valve should open. Check for gas pressure at |
|
| the manifold tap located just before the burner. If |
|
| there is no pressure, check the incoming gas supply |
|
| to be sure all manual valves are open and flexible |
|
| gas hose is properly connected. If gas is present |
|
| and coils of gas valve are energized, the gas valve is |
|
| probably defective. |
Flame will not stay lit | Hot Surface Ignitor | Six seconds after the gas valve opens, ignition must |
|
| occur. if flame is not detected, the ignition control |
|
| will shut off and lock out. To reset the ignition |
|
| control, turn off the burner switch for 45 seconds, |
|
| then turn on the burner switch to retry ignition. The |
|
| ignition control requires a minimum of 0.8 D.C. |
|
| microamps. To check flame sensing operation, |
|
| connect a digital multimeter (capable of measuring |
|
| D.C. |
|
| ignition control and the ground lead. |
|
| NOTE: This is a current measurement and the |
|
| meter must be connected in series. If these |
|
| readings are not achieved, replace the hot surface |
|
| ignitor. |
|
| NOTE: The D.C. micro amp test must be conducted |
|
| with the oven in low flame (bypass) operation. Turn |
|
| the temperature control to the lowest setting. |
Impinger II | 9 |