| Power Supply | If there is sufficient |
|
| will not stay lit, check for proper polarity of the 120 |
|
| VAC power supply. |
| Ignition Control | If there is sufficient |
|
| VAC polarity is correct, but the flame will not stay lit, |
|
| replace ignition control. |
|
| NOTE: Check for proper ground connection on |
| NOTE: Flame should be lit at | ignition control. |
|
| |
| this time. |
|
Low flame is on, | Temperature Control | Check for 120 VAC at terminal #7 |
but no main flame |
| to neutral on temperature control. If no voltage, |
|
| trace voltage back through centrifugal switch and hi- |
|
| limit. Turn the temperature adjustment knob to |
|
| maximum temperature position and check for 120 |
|
| VAC at the load terminal #8 and neutral. If 120 VAC |
|
| is present and unit is not heating, refer to |
|
| "Temperature Solenoid Valve" for next check. If 120 |
|
| VAC is not present, proceed. |
| Thermocouple Probe | WITH POWER ON AND THERMOCOUPLE LEADS |
|
| ATTACHED TO THE TEMPERATURE CONTROL |
|
| BOARD: Measure the D.C. millivolt output of these |
|
| leads. Refer to thermocouple chart in Section D for |
|
| proper readings. If these readings are not achieved, |
|
| replace the thermocouple. |
| Temperature Set | Disconnect the potentiometer leads |
| Potentiometer | from the board. Place ohm meter test leads on the |
|
| blue and green pot leads. Reading should be 1 K |
|
| ohms. Place meter leads across the blue and purple |
|
| pot leads and rotate knob from high to low. Repeat |
|
| on green and purple leads. Check for even rise and |
|
| fall of ohms reading to insure that there are no open |
|
| or dead spots in the potentiometer. Check each |
|
| lead to ground for shorts. Replace pot if it does not |
|
| meet the above test. |
| Temperature Solenoid | If 120 VAC is present on the |
| Valve | temperature control board at load terminal #8 to |
|
| neutral, check for voltage at temperature regulation |
|
| valve. If voltage is present, listen for valve to open |
|
| and close. Also check for opens or shorts in the coil. |
|
| Replace as necessary. |
Intermittent Heating | Thermal/Overload of Main Fan | The main fan motor and the burner blower motor are |
| and Burner Blower Motors | equipped with internal thermal protection and will |
|
| cease to operate if over heating occurs. As the |
|
| motors overheat and then cool, this will cause the |
|
| units to cycle on and off intermittently. This may be |
|
| caused by improper ventilation or preventive |
|
| maintenance. Also, most of the problems listed |
|
| under "Oven will not heat" can cause intermittent |
|
| failure. |
Conveyor will not run | Voltage Supply | Check incoming voltage supply at line 1 to neutral. |
|
| There should be a voltage reading of 120 VAC. If |
|
| not present, check breakers. |
| 10 Amp Fuse | Check and/or replace. |
| Fuseholder | Check and/or replace. |
| Fan Switch | See procedure for checking on Page 10. |
10 | Impinger II – Advantage Service Manual - Domestic |