To Access Service Port:

A service port cap protects the service port core from contamination and serves as the primary leak seal.

1.Remove service port cap with an appropriately sized wrench.

2.Connect gauge set to service port.

3.When testing is completed, replace service port cap and tighten as follows:

SWith torque wrench: Finger tighten and torque cap per table 1.

SWithout torque wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise.

11 12 1

2

1/6 TURN

 

 

10

 

 

98 7 6

543

 

Reinstall Stem Cap:

Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:

S With Torque Wrench: Finger tighten and then torque cap per table 1.

SWithout Torque Wrench: Finger tighten

and use an appropriately sized wrench to turn an additional 1/12 turn clockwise.

1/12 TURN

11 12

1

2

10

 

 

98 7

6

543

IMPORTANT

Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.

Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.

See the Lennox Service and Application Notes Corp.0807−L5 (C−08−1) for further details and information.