GAS REQUIREMENTS
Instructions | Gas Dryers |
| |
|
| ||
| NOTE : The gas service to a gas dryer must conform | ||
| with the local codes and ordinances or, in the absence | ||
| of local codes and ordinances, with the latest edition | ||
Safety | of the National Fuel Gas Code ANSI Z223.1/NFPA | ||
54 or the | |||
| |||
| Code. |
| |
| L.P (Liquefied Petroleum) Gas, 2,500 Btu/ft3 (93.1 | ||
| MJ/m3), service must be supplied at 10 | 1.5 in. water | |
Instructions | |||
column pressure. |
| ||
|
| ||
| NOTE : DO NOT connect the dryer to L.P. Gas | ||
Installation | Service without converting the gas valve. | ||
number. |
| ||
| L.P. gas conversion: |
| |
| In U.S.- Conversion must be made by a qualified | ||
| technician. |
| |
| See gas valve burner base for gas conversion kit part | ||
| In Canada- Conversion must be made by a licensed | ||
Instruction | |||
system by closing its individual manual | |||
| technician. Contact your local service | branch if you | |
| require further assistance. |
| |
| The dryer must be isolated from the gas supply piping | ||
Operating | during any pressure testing of the gas supply piping | ||
system at test presure equal to or less than 1/2 psi (3.45 | |||
| |||
| kPa). |
| |
| NOTE : When connecting to a gas line, an equipment | ||
| shutoff valve must be installed within 6 feet (1.8m) of | ||
Tips | the dryer. An 1/8 in. N.P.T. pipe plug must be | ||
installed as shown. Refer to Fig |
| ||
Troubleshooting |
| ||
Supply line requirements: |
| ||
|
| ||
| Provide a rigid gas supply line to the dryer location. | ||
| In U.S.- An individual manual shutoff valve must be | ||
| installed within 1.8m (6 feet) of the dryer in accordance | ||
| with the National Fuel Gas Code ANSI Z223.1*. | ||
| In Canada- An individual manual shutoff valve must be | ||
| installed in accordance with the | ||
Customer Service | CAN/CGA |
| |
|
| ||
|
|
|
When a rigid pipe is used it should be 1/2 inch IPS. When acceptable to the gas supplier and local codes, 3/8- inch approved tubing may be used for lengths under 6.1 m (20 feet). For lengths over 6.1m (20 feet), larger tubing should be used.
WARNING
To reduce the risk of gas leaks, fire or explosion:
•The dryer must be connected to the type of gas as shown on the nameplate located in the door recess.
•Use a new flexible stainless steel connector.
•Use pipe joint compound insoluble in L.P. (Liquefied Petroleum) Gas, or Teflon tape, on all pipe threads.
•Purge air and sediment from gas supply line before connecting it to the dryer. Before tightening the connection, purge remaining air from gas line to dryer until odor of gas is detected. This step is required to prevent a gas valve contamination.
•Do not use an open flame to check for gas leaks. Use a
•Any
1 8