LG Electronics LSU240CE, LSN090CE, LSU120CE, LSU090HE, LSU090CE, LSN180CE Pumping Down, Procedure

Models: LSN180HE LSN120HE LSN090CE, LSN120CE, LSN180CE, LSN240CE, LSN090HE, LSN120HE, LSN180HE, LSN240HE, LSU090CE, LSU120CE, LSU180CE, LSU240CE, LSU090HE, LSU120HE, LSU180HE, LSU240HE LSN240CE LSU240HE LSU090CE LSU240CE LSN120CE LSN180CE LSU120HE LSU180HE LSU180CE LSN090CE LSN240HE LSN090HE LSU090HE LSU120CE

1 83
Download 83 pages 59.19 Kb
Page 46
Image 46

Troubleshooting Guide

Pumping Down

Indoor unit

Liquid side

 

Open

Outdoor unit

2-Way valve

Gas side

Closed

3-Way valve

Lo

CLOSECLOSE

Purge the air

• Procedure

(1)Confirm that both the 2-way and 3-way valves are set to the open position.

Remove the valve stem caps and confirm that the valve stems are in the raised posi- tion.

Be sure to use a hexagonal wrench to operate the valve stems.

(2)Operate the unit for 10 to 15 minutes.

(3)Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way valve.

Connect the charge hose with the push pin to the service port.

(4)Air purging of the charge hose.

Open the low-pressure valve on the charge set slightly to air purge from the charge hose.

(5)Set the 2-way valve to the closed position.

(6)Operate the air conditioner at the cooling cycle and stop it when the gauge indi- cates 1kg/cm2g.

(7)Immediately set the 3-way valve to the closed position.

Do this quickly so that the gauge ends up indicating 3 to 5kg/cm2g.

(8)Disconnect the charge set, and mount the 2-way and 3-way valve’s stem nuts and the service port nut.

Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.

Be sure to check for gas leakage.

Do not use the existing charge set for R-22. It is necessary to use new charge set for R- 410A. The pressure of R-410A is 1.6 times higher than that of R-22. Thus, the high pres- sure side gauge of charge set should be used higher pressure gauge of 50kg/cm2 range.

46Room Air Conditioner