Troubleshooting Guide

Evacuation

(All amount of refrigerant leaked)

Indoor unit

Liquid side

 

 

 

 

 

Outdoor unit

 

3-Way

 

 

valve

Open

 

Gas side

 

 

3-Way

 

 

valve

Open

Vacuum pump

 

 

 

Lo

 

OPEN

CLOSE

 

• Procedure

(1)Connect the vacuum pump to the center hose of charge set center hose

(2)Evacuation for approximately one hour.

Confirm that the gauge needle has moved toward -76 cmHg (vacuum of 4 mmHg or less).

(3)Close the valve (Lo side) on the charge set, turn off the vacuum pump, and con- firm that the gauge needle does not move (approxima-tely 5 minutes after turning off the vacuum pump).

(4)Disconnect the charge hose from the vac- uum pump.

Vacuum pump oil.

If the vacuum pump oil becomes dirty or depleted, replenish as needed.

Use vacuum pump equipped with check value applied to be prevented from flowing backward.

48Room Air Conditioner

Page 48
Image 48