LG Electronics PG-100-2006-VER3 High Wall Duct- Free Flex Multi Split Dual & Tri Zone, Wire Size

Models: PG-100-2006-VER3

1 40
Download 40 pages 55.66 Kb
Page 25
Image 25
HIGH WALL DUCT- FREE • FLEX MULTI SPLIT • DUAL & TRI ZONE

HIGH WALL DUCT- FREE • FLEX MULTI SPLIT • DUAL & TRI ZONE

ELECTRICAL & REFRIGERATION QUICK REFERENCE

 

 

 

Electrical Specifications

 

 

 

Zone

Type

Model

BTUs

Voltage

Rated

MCA*

MOP**

 

 

 

 

Indoor

Outdoor

Amps

 

 

Flex Multi Split

A/C

LMN090CE

9,000

36V DC

0.5

Indoor Units

A/C

LMAN090CNS

9,000

36V DC

1.3

 

A/C

LMN120CE

12,000

36V DC

0.5

 

A/C

LMAN120CNS

12,000

36V DC

1.3

 

A/C

LMAN121CNM

12,000

36V DC

0.5

 

H/P

LMN090HE

9,000

36V DC

0.5

 

H/P

LMAN090HNS

9,000

36V DC

1.3

 

H/P

LMN120HE

12,000

36V DC

0.5

 

H/P

LMAN120HNS

12,000

36V DC

1.3

 

H/P

LMAN121HNM

12,000

36V DC

0.5

Outdoor Units

A/C

LMU240CE

24,000

 

230/208

11.1

20

20

 

A/C

LMU360CE

36,000

 

230/208

16.6

20

30

 

H/P

LMU240HE

24,000

 

230/208

11.1

20

20

 

H/P

LMU360HE

36,000

 

230/208

16.6

20

30

All equipment single phase.

*Minimum Circuit Ampacity

 

**Maximum Overcurrent Protection

NOTE: Please see local electrical codes for proper wire specifications.

Wire Size

Minimum AWG

14-3

Indoor/Outdoor Connecting Cable Minimum AWG

18-4

Refrigerant Line & Formula Specifications***

 

 

 

 

Pipe size

Additional

Max. length

Max.

 

Type

Model

BTUs

Liquid

Suction

Refrigerant

each pipe

elevation

Flex Multi Split

A/C

LMN090CE

9,000

1/4"

3/8"

0.21 oz./ft.

50'

25'

 

A/C

LMAN090CNS

9,000

1/4"

3/8"

0.21 oz./ft.

50'

25'

 

A/C

LMN120CE

12,000

1/4"

3/8"

0.21 oz./ft.

50'

25'

 

A/C

LMAN120CNS

12,000

1/4"

3/8"

0.21 oz./ft.

50'

25'

 

A/C

LMAN121CNM

12,000

1/4"

3/8"

0.21 oz./ft.

50'

25'

 

H/P

LMN090HE

9,000

1/4"

3/8 "

0.21 oz./ft.

50'

25'

 

H/P

LMAN090HNS

9,000

1/4"

3/8"

0.21 oz./ft.

50'

25'

 

H/P

LMN120HE

12,000

1/4"

3/8"

0.21 oz./ft.

50'

25'

 

H/P

LMAN120HNS

12,000

1/4"

3/8"

0.21 oz./ft.

50'

25'

 

H/P

LMAN121HNM

12,000

1/4"

3/8"

0.21 oz./ft.

50'

25'

***Dual Zone: exterior unit has sufficient refrigerant for charging two indoor coils and a 25 ft. line set per indoor unit. Tri Zone: exterior unit has sufficient refrigerant for charging three indoor coils and a 25 ft. line set per indoor unit.

NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement installations) have the following additional requirement:

For systems with maximum elevation of 25 ft. (see chart above and Figure A), refrigerant lines must be oil trapped between 8 ft. and 16.4 ft. of elevation.

For systems with elevation of greater than 25 ft. (see chart above), refrigerant lines must be oil trapped at least every 16.4 ft. of elevation.

 

OUTDOOR UNIT

OIL TRAP

 

INDOOR UNIT

25' maximum

 

 

8' minimum

 

16.4' maximum

Figure A.

Example: 25 ft. maximum elevation.

23

Page 25
Image 25
LG Electronics PG-100-2006-VER3 manual High Wall Duct- Free Flex Multi Split Dual & Tri Zone, Electrical Specifications