DUCT- FREE • FLOOR STANDING & CEILING CASSETTE • SINGLE ZONE

DUCT- FREE • FLOOR STANDING & CEILING CASSETTE • SINGLE ZONE

ELECTRICAL & REFRIGERATION QUICK REFERENCE

Electrical Specifications

 

Type

System #

BTUs

Voltage

Rated

MCA*

MOP**

 

 

 

 

Indoor

Outdoor

Amps

 

 

Floor Standing

A/C

LF300CP

28,000

230/208

230/208

11.5/11.5

17***

25***

 

A/C

LF480CP

48,000

230/208

230/208

20.0/20.0

28.9***

50***

 

 

 

 

 

 

 

 

 

Ceiling Cassette

A/C

LC240CP

24,000

230/208

230/208

11.5/12.4

17.3

30

 

A/C

LC340CP

34,000

230/208

230/208

15.1/16.5

27.5

50

All equipment single phase.

NOTE: Please see local electrical codes for proper wire specifications.

*Minimum Circuit Ampacity

**Maximum Overcurrent Protection

***Floor standing MCA + MOP calculated for indoor and outdoor units connected to common breaker (Preferred method).

Wire Size

Minimum AWG

14-3

Indoor/Outdoor Connecting Cable Minimum AWG

14-3

Refrigerant Line Specifications

 

 

 

 

Pipe size

Additional

Max. length

Max.

 

Type

System #

BTUs

Liquid

Suction

Refrigerant

each pipe

elevation

Floor Standing

A/C

LF300CP

28,000

3/8"

5/8"

0.32 oz./ft.

100'

66'

 

A/C

LF480CP

48,000

3/8"

3/4"

0.42 oz./ft.

131'

82'

 

 

 

 

 

 

 

 

 

Ceiling Cassette

A/C

LC240CP

24,000

1/4"

1/2"

0.32 oz./ft.

100'

50'

 

A/C

LC340CP

34,000

1/4"

5/8"

0.42 oz./ft.

115'

66'

Each system is pre-charged with enough refrigerant to charge 25 ft. of line and the interior unit.

NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement installations) have the following additional requirement:

For systems with maximum elevation of 25 ft. (see chart above and Figure A), refrigerant lines must be oil trapped between 8 ft. and 16.4 ft. of elevation.

For systems with elevation of greater than 25 ft. (see chart above), refrigerant lines must be oil trapped at least every 16.4 ft. of elevation.

 

OUTDOOR UNIT

OIL TRAP

 

INDOOR UNIT

25' maximum

 

 

8' minimum

 

16.4' maximum

Figure A.

Example: 25 ft. maximum elevation.

29