Liebert EM manual MP Advanced Power Strip Thresholds

Models: EM

1 48
Download 48 pages 55.09 Kb
Page 20
Image 20
4.4.3MP Advanced Power Strip Thresholds

Web Interface Overview

4.4.3MP Advanced Power Strip Thresholds

When using the OpenComms EM to monitor MP Advanced Power Strips, you may set thresholds that will trigger alerts for power, voltage, current and temperature sensors in each power strip.

Each sensor has four thresholds: High Critical, High Warning, Low Warning and Low Critical. The Normal range is determined by these limits. Table 9 shows examples of limits for these types of sen- sors. Each level is color-coded in the Web interface for easy identification.

Table 9 Examples of sensor limits - MP Advanced power strip sensors

 

 

Examples of Limits

 

Text Display Color

Graph

 

 

 

 

 

 

 

 

Power

Voltage

Current

Temperature

Serial Port

Status &

Line

Limit

(Watts)

(VAC)

(Amps)

(°F)

Name

Current Value

Color

High Critical

2400

132

20

85

Red

Red

Red

 

 

 

 

 

 

 

 

High Warning

1900

126

16

75

Yellow

Yellow

Yellow

 

 

 

 

 

 

 

 

Low Warning

1000

114

8

65

Yellow

Yellow

Yellow

 

 

 

 

 

 

 

 

Low Critical

500

108

4

60

Red

Red

Red

 

 

 

 

 

 

 

 

Other conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

1 to 6999

115 to 125

0.1 to 19.9

66°F to 74°F

Green

Green

 

 

 

 

 

 

 

 

Not Present

 

(sensor is not connected)

Gray

Black

 

 

 

 

 

 

 

 

Using the examples of temperature sensor limits in Table 7, the following is a typical scenario:

The temperature of a monitored area rises to 90°F. The status changes at two points:

The status changes to High Warning when the temperature reaches 75°F. The serial port name, current reading and status are displayed in yellow text in the Web interface.

As the temperature continues to rise, the status changes to High Critical at 85°F (displayed in red text).

At each change in status, the unit sends alerts if it is configured to do so.

When the temperature falls to 74°F, the status changes to Normal (displayed in green text) and a return-to-normal alert is sent if the unit is configured to send alerts.

When the serial cable is disconnected from the unit, the status changes to Not Present (black text) and the serial port’s name appears in gray text.

14

Page 20
Image 20
Liebert EM manual MP Advanced Power Strip Thresholds, Examples of sensor limits - MP Advanced power strip sensors