Ground Bonding Screw
A ground bond-
ing screw is pro-
vided on the rear
of the unit. This
feature is pro-
vided as an
attachment point
for conductors
the rack may
contain for the
purpose of func-
tional grounding
or bonding of
ungrounded
metal parts.
Ground cables
are not included.
Note: The Ground Bonding wire must be a minimum of 10 AWG to maintain
proper grounding.
Connecting Devices
Make sure that
the devicescon-
nected do not
exceed the unit
capabilities.
This Dual Input
Micro Smart-
Switch features
3 output recepta-
cles per circuit
breaker, for a
total of 12
receptacles.
This model is
rated at 10A per
breaker.
Each block of 3
receptacles has a maximum output rating of 10A. If the total connected load
exceeds 10A, the circuit breaker will trip and interrupt power to all loads attached
to that block of receptacles.
The maximum output of this Micro SmartSwitch is 24A. If the total load con-
nected to all load segments exceed 24A, the circuit breaker at the wall could trip
and interrupt power to all loads.
DISCONTINUED
PROD U C T