Electrical Installation

Table 4

Current ratings—battery

 

 

 

 

 

 

 

UPS Rating

 

Maximum Battery

External Breaker

 

 

 

 

kVA

 

kW

Nominal VDC

Current at EOD

Trip, Amps

 

 

 

 

 

 

250

 

225

480

615

700

300

 

270

480

737

800

 

 

 

 

 

 

400

 

360

480

981

1000

 

 

 

 

 

 

Notes on Tables

1.Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in NEC 100. Maximum input current is controlled by the current limit setting which is adjustable. Values shown are for maximum setting of 125%. Standard factory setting is 125%.

2.Recommended bypass external overcurrent protection is based on 125% overload capacity for 10 minutes.

3.All recommended external overcurrent protections are based on 80% rated breakers.

4.Nominal battery voltage is shown at 2.0 volts / cell.

Table 5 Recommended conduit and cable sizes

Rectifier Input

 

 

 

 

Voltage

 

Nominal Selection

Alternate Selection

UPS Rating

 

 

 

 

 

 

 

 

 

(VAC)

 

Top Cable Entry Input

Bottom Cable Entry

Top Cable Entry Input

Bottom Cable Entry

 

 

 

 

 

 

Wire & Conduit

Input Wire & Conduit

Wire & Conduit

Input Wire & Conduit

kVA

kW

Input

 

Bypass

Output

Ph, G THW / FMC

Ph, G THW / RNC

Ph, G THW / FMC

Ph, G THW / RNC

 

 

 

 

 

 

 

 

 

 

250

225

480

 

480

480

(2) 2.5C 3-250kcmil,

(2) 2.5C 3-250kcmil,

(3) 2C 3-#2/0AWG,

(3) 2C 3-#2/0AWG,

 

#1/0AWG

#1/0AWG

#1/0AWG

#1/0AWG

 

 

 

 

 

 

300

270

480

 

480

480

(2) 3C 3-350kcmil,

(2) 3C 3-350kcmil,

(3) 2.5C 3-#4/0AWG,

(3) 2.5C 3-#4/0AWG,

 

#1/0AWG

#1/0AWG

#1/0AWG

#1/0AWG

 

 

 

 

 

 

400

360

480

 

480

480

(2) 3C 3-500kcmil,

(2) 3.5C 3-500kcmil,

(3) 2.5C 3-250kcmil,

(3) 2.5C 3-250kcmil,

 

#1/0AWG

#1/0AWG

#1/0AWG

#1/0AWG

 

 

 

 

 

 

Bypass Input

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Selection

Alternate Selection

UPS Rating

 

Voltage (VAC)

 

 

 

 

 

Top Cable Entry Input

Bottom Cable Entry

Top Cable Entry Input

Bottom Cable Entry

 

 

 

 

 

 

Wire & Conduit

Input Wire & Conduit

Wire & Conduit

Input Wire & Conduit

kVA

kW

Input

 

Bypass

Output

Ph, N, G THW / FMC

Ph, N, G THW / RNC

Ph, N, G THW / FMC

Ph, N, G THW / RNC

 

 

 

 

 

 

 

 

 

 

250

225

480

 

480

480

(3) 2.5C 3-#2/0AWG,

(3) 3C 3-#2/0AWG,

(2) 3C 3-250kcmil,

(2) 3C 3-250kcmil,

 

2-#1/0AWG, #1/0AWG

2-#1/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

300

270

480

 

480

480

(3) 2.5C 3-#4/0AWG,

(3) 3C 3-#4/0AWG,

(2) 3C 3-350kcmil,

(2) 3.5C 3-350kcmil,

 

2-#1/0AWG, #1/0AWG

2-#1/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

400

360

480

 

480

480

(3) 3C 3-250kcmil,

(3) 3C 3-250kcmil,

(2) 3.5C 3-500kcmil,

(2) 4C 3-500kcmil,

 

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

2-350kcmil, #1/0AWG

2-350kcmil, #1/0AWG

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Selection

Alternate Selection

UPS Rating

 

Voltage (VAC)

 

 

 

 

 

Top Cable Entry Input

Bottom Cable Entry Input

Top Cable Entry Input

Bottom Cable Entry

 

 

 

 

 

 

Wire & Conduit

Wire & Conduit

Wire & Conduit

Input Wire & Conduit

kVA

kW

Input

 

Bypass

Output

Ph, N, G THW / FMC

Ph, N, G THW / RNC

Ph, N, G THW / FMC

Ph, N, G THW / RNC

 

 

 

 

 

 

 

 

 

 

250

225

480

 

480

480

(3) 2.5C 3-#2/0AWG,

(3) 3C 3-#2/0AWG,

(3) 2.5C 3-#2/0AWG,

(3) 3C 3-#2/0AWG,

 

2-#1/0AWG, #1/0AWG

2-#1/0AWG, #1/0AWG

2-#1/0AWG, #1/0AWG

2-#1/0AWG, #1/0AWG

 

 

 

 

 

 

300

270

480

 

480

480

(3) 2.5C 3-#4/0AWG,

(3) 3C 3-#4/0AWG,

(3) 2.5C 3-#4/0AWG,

(3) 3C 3-#4/0AWG,

 

2-#1/0AWG, #1/0AWG

2-#1/0AWG, #1/0AWG

2-#1/0AWG, #1/0AWG

2-#1/0AWG, #1/0AWG

 

 

 

 

 

 

400

360

480

 

480

480

(3) 3C 3-250kcmil,

(3) 3C 3-250kcmil,

(3) 3C 3-250kcmil,

(3) 3C 3-250kcmil,

 

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Selection

Alternate Selection

UPS Rating

 

Voltage (VAC)

 

 

 

 

 

Top Cable Entry Input

Bottom Cable Entry Input

Top Cable Entry Input

Bottom Cable Entry Input

 

 

 

 

 

 

Wire & Conduit

Wire & Conduit

Wire & Conduit

Wire & Conduit

kVA

kW

Input

 

Bypass

Output

Wires, G THW / FMC

Wires, G THW / RNC

Wires, G THW / FMC

Wires, G THW / RNC

 

 

 

 

 

 

 

 

 

 

250

225

480

 

480

480

(2) 2.5C 2-350kcmil,

(2) 2.5C 2-350kcmil,

(3) 2C 2-#4/0AWG,

(3) 2C 2-#4/0AWG,

 

#1/0AWG

#1/0AWG

#1/0AWG

#1/0AWG

 

 

 

 

 

 

300

270

480

 

480

480

(2) 2.5C 2-500kcmil,

(2) 3C 2-500kcmil,

(3) 2C 2-250kcmil,

(3) 2C 2-250kcmil,

 

#1/0AWG

#1/0AWG

#1/0AWG

#1/0AWG

 

 

 

 

 

 

400

360

480

 

480

480

(3) 2.5C 2-500kcmil,

(3) 3C 2-500kcmil,

(4) 2C 2-250kcmil,

(4) 2.5C 2-250kcmil,

 

#4/0AWG

#4/0AWG

#4/0AWG

#4/0AWG

 

 

 

 

 

 

If the UPS is used in a four-wire system, the neutral ground jumper must be removed.