Electrical Installation

7

Notes on Tables

1. Nominal input current (considered continuous) is based on full-rated output load. Maximum

current includes nominal input current and maximum battery recharge current (considered

noncontinuous). Continuous and noncontinuous current are defined in NEC 100. Maximum input

current is controlled by the current limit setting which is adjustable. Values shown are for

maximum setting of 125%. Standard factory setting is 125%.

2. Recommended bypass external overcurrent protection is based on 125% overload capacity for 10

minutes.

3. All recommended external overcurrent protections are based on 80% rated breakers.

4. Nominal battery voltage is shown at 2.0 volts / cell.

Table 4 Current ratings—battery

UPS Rating

Nominal VDC

Maximum Battery

Current at EOD

External Breaker

Trip, AmpskVA kW

250 225 480 615 700

300 270 480 737 800

400 360 480 981 1000

Table 5 Recommended conduit and cable sizes

Rectifier Input

UPS Rating
Voltage
(VAC)
Nominal Selection Alternate Selection
Top Cable Entry Input
Wire & Conduit
Ph, G THW / FMC
Bottom Cable Entry
Input Wire & Conduit
Ph, G THW / RNC
Top Cable Entry Input
Wire & Conduit
Ph, G THW / FMC
Bottom Cable Entry
Input Wire & Conduit
Ph, G THW / RNCkVA kW Input Bypass Output
250 225 480 480 480 (2) 2.5C 3-250kcmil,
#1/0AWG
(2) 2.5C 3-250kcmil,
#1/0AWG
(3) 2C 3-#2/0AWG,
#1/0AWG
(3) 2C 3-#2/0AWG,
#1/0AWG
300 270 480 480 480 (2) 3C 3-350kcmil,
#1/0AWG
(2) 3C 3-350kcmil,
#1/0AWG
(3) 2.5C 3-#4/0AWG,
#1/0AWG
(3) 2.5C 3-#4/0AWG,
#1/0AWG
400 360 480 480 480 (2) 3C 3-500kcmil,
#1/0AWG
(2) 3.5C 3-500kcmil,
#1/0AWG
(3) 2.5C 3-250kcmil,
#1/0AWG
(3) 2.5C 3-250kcmil,
#1/0AWG

Bypass Input

UPS Rating Voltage (VAC)
Nominal Selection Alternate Selection
Top Cable Entry Input
Wire & Conduit
Ph, N, G THW / FMC
Bottom Cable Entry
Input Wire & Conduit
Ph, N, G THW / RNC
Top Cable Entry Input
Wire & Conduit
Ph, N, G THW / FMC
Bottom Cable Entry
Input Wire & Conduit
Ph, N, G THW / RNCkVA kW Input Bypass Output
250 225 480 480 480 (3) 2.5C 3-#2/0AWG,
2-#1/0AWG, #1/0AWG
(3) 3C 3-#2/0AWG,
2-#1/0AWG, #1/0AWG
(2) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
(2) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
300 270 480 480 480 (3) 2.5C 3-#4/0AWG,
2-#1/0AWG, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#1/0AWG, #1/0AWG
(2) 3C 3-350kcmil,
2-#4/0AWG, #1/0AWG
(2) 3.5C 3-350kcmil,
2-#4/0AWG, #1/0AWG
400 360 480 480 480 (3) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
(3) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
(2) 3.5C 3-500kcmil,
2-350kcmil, #1/0AWG
(2) 4C 3-500kcmil,
2-350kcmil, #1/0AWG

Output

UPS Rating Voltage (VAC)
Nominal Selection Alternate Selection
Top Cable Entry Input
Wire & Conduit
Ph, N, G THW / FMC
Bottom Cable Entry Input
Wire & Conduit
Ph, N, G THW / RNC
Top Cable Entry Input
Wire & Conduit
Ph, N, G THW / FMC
Bottom Cable Entry
Input Wire & Conduit
Ph, N, G THW / RNCkVA kW Input Bypass Output
250 225 480 480 480 (3) 2.5C 3-#2/0AWG,
2-#1/0AWG, #1/0AWG
(3) 3C 3-#2/0AWG,
2-#1/0AWG, #1/0AWG
(3) 2.5C 3-#2/0AWG,
2-#1/0AWG, #1/0AWG
(3) 3C 3-#2/0AWG,
2-#1/0AWG, #1/0AWG
300 270 480 480 480 (3) 2.5C 3-#4/0AWG,
2-#1/0AWG, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#1/0AWG, #1/0AWG
(3) 2.5C 3-#4/0AWG,
2-#1/0AWG, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#1/0AWG, #1/0AWG
400 360 480 480 480 (3) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
(3) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
(3) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
(3) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG

Battery

UPS Rating Voltage (VAC)
Nominal Selection Alternate Selection
Top Cable Entry Input
Wire & Conduit
Wires, G THW / FMC
Bottom Cable Entry Input
Wire & Conduit
Wires, G THW / RNC
Top Cable Entry Input
Wire & Conduit
Wires, G THW / FMC
Bottom Cable Entry Input
Wire & Conduit
Wires, G THW / RNCkVA kW Input Bypass Output
250 225 480 480 480 (2) 2.5C 2-350kcmil,
#1/0AWG
(2) 2.5C 2-350kcmil,
#1/0AWG
(3) 2C 2-#4/0AWG,
#1/0AWG
(3) 2C 2-#4/0AWG,
#1/0AWG
300 270 480 480 480 (2) 2.5C 2-500kcmil,
#1/0AWG
(2) 3C 2-500kcmil,
#1/0AWG
(3) 2C 2-250kcmil,
#1/0AWG
(3) 2C 2-250kcmil,
#1/0AWG
400 360 480 480 480 (3) 2.5C 2-500kcmil,
#4/0AWG
(3) 3C 2-500kcmil,
#4/0AWG
(4) 2C 2-250kcmil,
#4/0AWG
(4) 2.5C 2-250kcmil,
#4/0AWG
If the UPS is used in a four-wire system, the neutral ground jumper must be removed.