MINI-TOWER SPECIFICATIONS

Model Number

PS700MT-230

 

PS1000MT-230

PS1400MT-230

 

PS2200MT-230

Model Rating VA/W

700 / 450

 

1000 / 670

1400 / 950

 

2200 / 1600

DIMENSIONS: mm (in)

 

 

 

 

 

 

 

Unit

W x D x H

140 x 365 x 178

 

172 x 447 x 227

172 x 447 x 227

 

194 x 511 x 336

 

 

(5.5 x 14.4 x 7.0)

 

(6.8 x 17.5 x 8.9)

(6.8 x 17.5 x 8.9)

 

(7.6 x 20.1 x 13.2)

Shipping W x D x H

265 x 492 x 300

 

307 x 581 x

307 x 581 x 358

 

330 x 635 x 470

 

 

(10.5x19.2x11.75)

 

358 (12.0 x 22.25 x

(12.0 x 22.25 x 14)

 

(13.0 x 25.0 x 18.5)

 

 

 

 

 

14)

 

 

 

WEIGHT: kg (lbs)

 

 

 

 

 

 

 

Unit

 

13.6

(29.9)

 

19.7 (43.4)

22.5 (49.4)

 

37.1 (81.7)

Shipping

15.0 (33.1)

 

21.1 (46.5)

23.9 (52.5)

 

39.5 (87.0)

INPUT AC PARAMETERS

 

 

 

 

 

 

 

Voltage Range

 

 

 

230 VAC; -27%, +18%

 

Voltage Raise

Maintains output to 230 VAC; -19%, when input is 230 VAC, -27%

Voltage Lower

Maintains output to 230 VAC; +8%, when input is 230 VAC, +18%

Frequency

 

 

 

45-55 Hz or 55-65 Hz; auto sensing

 

Input

Connector

IEC 320-10A

 

IEC 320-10A

IEC 320-10A

 

IEC-320-16A

OUTPUT AC PARAMETERS

 

 

 

 

 

 

 

Output Sockets

(4) IEC 320-10A

 

(4) IEC 320-10A

(4) IEC 320-10A

 

(4) IEC320-10A,

 

 

 

 

 

 

 

 

(1) IEC-320-16A

Voltage

 

 

 

186 VAC to 248 VAC

 

Max. Current Rating

3.0 A

 

4.3 A

6.1 A

 

9.6 A

Frequency

 

 

 

50 Hz or 60 Hz

 

Waveform

 

 

 

Sinewave

 

Mains Mode Overload

 

 

200% for > 2 cycles; 110% for > 5 minutes

Battery Mode Overload

 

 

150% for > 1 cycle; 110% for > 30 seconds

BATTERY PARAMETERS

 

 

 

 

 

 

 

Type

 

 

 

 

Valve-regulated, nonspillable, lead acid

 

Qty. x Voltage x Rating

2 x 12V x 7.0 or 7.2 AH

 

3 x 12V x 7.0 or 7.2 AH

4 x 12V x 7.0 or 7.2 AH

 

8 x 6V x 12 AH

 

 

 

 

 

 

 

Batt. Mfg./ Part Number

CSB: GP1270F2 or Panasonic LC-R127R2CH1

 

Panasonic:

 

 

 

 

 

 

 

 

LC-R0612CH1

Transfer Time

 

 

2-6 ms typical, includes detect and transfer

Back-up Time

 

 

 

See Typical Battery Discharge Curves

 

Recharge Time

 

3 Hours to 95% capacity, after full discharge into 100% load

ENVIRONMENTAL

 

 

 

 

 

 

 

Operating Temperature

 

 

 

0° C to +40° C (+32° F to + 104° F)

 

Storage Temperature

 

 

 

-15° C to +50° C (+5° F to + 122° F)

 

Relative Humidity

 

 

 

0% to 95%, non-condensing

 

Operating Elevation

 

Up to 10,000 ft. (3000 m) at 35° C without derating

Storage Elevation

 

 

 

15,000 m (50,000 ft.) maximum

 

Audible Noise

 

 

 

<45 dBA at 1 meter

 

AGENCY

 

 

 

 

 

 

 

Safety

 

TUV/GS Listed, CE Low Voltage Directive compliant

RFI/EMI

 

EN 55022, Class B; CE EMC Directive compliant

Immunity

IEC 801-2, Level 4 / IEC 801-3, Level 3 / IEC 801-4, Level 4 / IEC 801-5, Level 3

RACKMOUNT SPECIFICATIONS

Model Number

PS700RM-230

 

PS1000RM-230

PS1400RM-230

 

PS2200RM-230

Model Rating VA/W

700 / 450

 

1000 / 670

1400 / 950

 

2200 / 1600

DIMENSIONS: mm (in)

 

 

 

 

 

 

Unit

W x D x H

483 x 457 x 133

 

483 x 457 x 133

483 x 457 x 133

 

483 x 457 x 178

 

 

(19 x 18 x 5.25)

 

(19 x 18 x 5.25)

(19 x 18 x 5.25)

 

(19 x 18 x 7)

Shipping W x D x H

699 x 610 x 279

 

699 x 610 x 279

699 x 610 x 279

 

699 x 610 x 305

 

 

(27.5 x 24 x 11)

 

(27.5 x 24 x 11)

(27.5 x 24 x 11)

 

(27.5 x 24 x 12)

WEIGHT: kg (lbs)

 

 

 

 

 

 

Unit

 

18.9 (41.5)

 

23.3 (51.3)

26.0 (57.2)

 

39.1 (86.0)

Shipping

23.1 (50.8)

 

27.2 (59.9)

30.0 (66.1)

 

43.3 (95.3)

INPUT AC PARAMETERS

 

 

 

 

 

 

Voltage Range

 

 

230 VAC; -27%, +18%

 

Voltage Raise

Maintains output to 230 VAC; -19%, when input is 230 VAC, -27%

Voltage Lower

Maintains output to 230 VAC; +8%, when input is 230 VAC, +18%

Frequency

 

 

45-55 Hz or 55-65 Hz; auto sensing

 

Input

Connector

IEC 320-10A

 

IEC 320-10A

IEC 320-10A

 

IEC-320-16A

OUTPUT AC PARAMETERS

 

 

 

 

 

 

Output Sockets

(4) IEC 320-10A

 

(4) IEC 320-10A

(4) IEC 320-10A

 

(4) IEC320-10A,

 

 

 

 

 

 

 

(1) IEC-320-16A

Voltage

 

 

186 VAC to 248 VAC

 

Max. Current Rating

3.0 A

 

4.6 A

6.1 A

 

9.6 A

Frequency

 

 

50 Hz or 60 Hz

 

Waveform

 

 

Sinewave

 

Mains Mode Overload

 

200% for > 2 cycles; 110% for > 5 minutes

 

Battery Mode Overload

 

150% for > 1 cycle; 110% for > 30 seconds

 

BATTERY PARAMETERS

 

 

 

 

 

 

Type

 

 

 

Valve-regulated, nonspillable, lead acid

 

Qty. x Voltage x Rating

2 x 12V x 7.0 or 7.2 AH

 

3 x 12V x 7.0 or 7.2 AH

4 x 12V x 7.0 or 7.2 AH

 

8 x 6V x 12 AH

 

 

 

 

 

 

Batt. Mfg./ Part Number

CSB: GP1270F2 or Panasonic LC-R127R2CH1

 

Panasonic:

 

 

 

 

 

 

 

LC-R0612CH1

Transfer Time

 

2-6 ms typical, includes detect and transfer

 

Back-up Time

 

 

See Typical Battery Discharge Curves

 

Recharge Time

3 Hours to 95% capacity, after full discharge into 100% load

ENVIRONMENTAL

 

 

 

 

 

 

Operating Temperature

 

 

0° C to +40° C (+32° F to + 104° F)

 

Storage Temperature

 

 

-15° C to +50° C (+5° F to + 122° F)

 

Relative Humidity

 

 

0% to 95%, non-condensing

 

Operating Elevation

Up to 10,000 ft. (3000 m) at 35° C without derating

Storage Elevation

 

 

15,000 m (50,000 ft.) maximum

 

Audible Noise

 

 

<45 dBA at 1 meter

 

AGENCY

 

 

 

 

 

 

Safety

TUV/GS Listed, CE Low Voltage Directive compliant

RFI/EMI

EN 55022, Class B; CE EMC Directive compliant

Immunity

IEC 801-2, Level 4 / IEC 801-3, Level 3 / IEC 801-4, Level 4 / IEC 801-5, Level 3

25

26

 

Page 13
Image 13
Liebert Power Supply MINI-TOWER Specifications, Rackmount Specifications, Environmental, Agency