Specifications
27
Agency
Safety EN 62040-1-1; TUV/GS listed; CE compliance mark
Surge EN61000-4-5, Level 3, Criteria B
ESD EN61000-4-2, Level 3, Criteria B
Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Emissions EN 50091-2, Class B
Conducted Immunity EN61000-4-6
Harmonics EN61000-3-2
Flicker EN61000-3-3
Transportation ISTA Procedure 1A Certification
Table 4 Battery cabinet specifications
Model Number PS2-48VBATT PS2-72VBATT
Used w/UPS Model PS1000RT2-230
PS1440RT2-230
PS2200RT2-230
PS3000RT2-230
Dimensions, W x D x H, mm (in)
Unit 87 x 557 x 430 (3.43 x 22 x 17) 87 x 612 x 430 (3.43 x 24.1 x 17)
Shipping 300 x 706 x 598
(11.8 x 27.8 x 23.5)
333 x 864 x 598
(13.1 x 34 x 23.5)
Weight, kg (lbs)
Unit 30 (66.1) 46 (101.4)
Shipping 38.6 (85.1) 53.6 (118.1)
Battery Parameter
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating 2 strings of 4 x 12V x 7Ah 2 strings of 6 x 12V x 9Ah
Battery Manufacturers CSB, B&B Battery and EnerSys
Backup Time See Table 5 - Battery run times
Environmental
Operating Temperature 0°C to + 40°C (+32°F to + 104°F)
Storage Temperature -15°C to + 40°C (+5°F to + 104°F)
Relative Humidity 0% to 95%, non-condensing
Operating Altitude Up to 3,000m (10,000 ft) at 35°C (95°F) without derating
Agency
Safety EN 62040-1-1; TUV/GS listed; CE compliance mark
Emissions EN 50091-2, Class B
Transportation ISTA Procedure 1A Certification
Table 3 UPS specifications (continued)
Model Number PS1000RT2-230 PS1440RT2-230 PS2200RT2-230
PS2200RT2-230E
PS3000RT2-230
PS3000RT2-230E