![](/images/new-backgrounds/1117988/11798843x1.webp)
Modes of Operation
7.3Battery Mode
The UPS switches to Battery mode in the event of an extreme input voltage/frequency condition or complete mains failure. The battery system supplies power through the Inverter (1000VA & 1440VA) or through the
When the UPS is in Battery mode, the Battery Indicator illuminates green and an alarm sounds every 10 seconds. As capacity decreases, fewer indicators remain illuminated. Figure 15 shows the UPS in Battery mode with 61% - 80% battery capacity remaining.
Figure 15 Battery mode at 61 – 80% battery capacity
Battery Indicator illuminated
When a low battery condition occurs, the Battery Indicator flashes green and the alarm sounds every
Figure 16 Low Battery mode
Battery Indicator flashes green
For approximate battery run times, refer to Table 5 - Battery run times. These run times are approximates based on resistive load and an ambient temperature of 25°C (77°F). To increase this time, turn Off
! CAUTION
Turning Off the UPS while it is in battery mode will result in loss of output power.
7.4Battery Recharge Operation
Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging.
18