Liebert PSITM user manual Battery Mode, Battery Recharge Operation, Battery Indicator illuminated

Models: PSITM

1 34
Download 34 pages 25.05 Kb
Page 22
Image 22

Modes of Operation

7.3Battery Mode

The UPS switches to Battery mode in the event of an extreme input voltage/frequency condition or complete mains failure. The battery system supplies power through the Inverter (1000VA & 1440VA) or through the DC-to-DC converter to the Bi-Directional Converter (2200VA & 3000VA) to generate power for the connected equipment.

When the UPS is in Battery mode, the Battery Indicator illuminates green and an alarm sounds every 10 seconds. As capacity decreases, fewer indicators remain illuminated. Figure 15 shows the UPS in Battery mode with 61% - 80% battery capacity remaining.

Figure 15 Battery mode at 61 – 80% battery capacity

Battery Indicator illuminated

When a low battery condition occurs, the Battery Indicator flashes green and the alarm sounds every half-second. The default low battery warning is two (2) minutes but can be configured via MultiLink. For more information, refer to 11.0 - Troubleshooting.

Figure 16 Low Battery mode

Battery Indicator flashes green

For approximate battery run times, refer to Table 5 - Battery run times. These run times are approximates based on resistive load and an ambient temperature of 25°C (77°F). To increase this time, turn Off non-essential pieces of equipment, such as idle computers and monitors, or add exter- nal battery cabinets.

! CAUTION

Turning Off the UPS while it is in battery mode will result in loss of output power.

7.4Battery Recharge Operation

Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging.

18

Page 22
Image 22
Liebert PSITM Battery Mode, Battery Recharge Operation, Battery Indicator illuminated, Battery Indicator flashes green