CONDITIONS OF USE: The mains supply socket must be within 2m (6.5 ft.) of the UPS and be eas- ily accessible.
Your UPS provides conditioned power to connected equipment. This product is designed for Commer- cial use only. It is not intended for use with life support and other designated “critical” devices. Maxi- mum load must not exceed that shown on the UPS rating label. If uncertain, consult your local dealer, Liebert representative or the Liebert Worldwide Support Group.
The PSI 1000 VA, and 1440 VA models are not supplied with an input power cable for connection to the mains supply socket. Use the input mains supply power cable from your data processing equip- ment to connect the UPS to the mains supply.
For the 2200 VA and 3000VA models, use the supplied
! CAUTION
The UPS and connected load total earth leakage current must not exceed 3.5mA. If the connected load earth leakage current is likely to exceed 2.5mA or you are unsure, then convert the input cable attachment to either a fixed wiring installation or an industrial plug/socket (e.g., CEE 17 connector). This alteration should be carried out by a competent electrical engineer who is conversant with local electrical codes and regulations.
When installing the UPS or making input and output connections, comply with relevant safety codes and standards (e.g. IEC60950, VDE0805,
Placing magnetic storage media on top of the UPS may result in data corruption.
The equipment can be installed and operated by individuals without previous training.
! CAUTION
DO NOT CONNECT equipment that could overload the UPS or demand
! CAUTION
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from the batteries.
A battery can present a risk of electrical shock and high
•Remove watches, rings, and other metal objects.
•Use tools with insulated handles.
•Do not dispose battery or batteries in a fire. The battery may explode.
•Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and eyes. It is toxic.
•When replacing the battery, use same number and type of battery as the suitable recom- mended type of battery listed in Table 3.
•Handle, transport and recycle batteries in accordance with local regulations.
Electromagnetic
Provided are a Liebert MultiLink cable and a USB cable for connection to a computer. Do not use the Liebert MultiLink cable for other applications. Store in a safe place if not required at this time.
When using the communication features on this UPS, ensure the cabling connected to the