16
OPTIONS

Contact your Liebert UPS distributor for option availability and ordering information.

Distribution

Configurable Distribution (CD)

An optional enclosure hardwires to 3.5 - 12 kVA units and accommodates up to eight Standard or Power Management Load

Modules. It may be wall or floor-mounted and includes a 70 Amp circuit breaker. Refer to drawings below.

2x4 Wall Stud
Wall Material (REF)BACK VIEW
19
(REF)
Rack may be mounted 4“ to the
right or left of location shown.
16“(REF)
TOP
VIEW
Rack Mat’l¼ Washer
¼ Split Loc
¼ 20 Nut
Bracket
¼ 20x1.0
Bolt
Detail ATB2
L1
L1
L2
L2
N
N
TB1
This terminal
block allows for
daisy-chaining
of additional
distribution
units.
Customer
Output
Power Management
Communications Connector
RIGHT
SIDE
OutputTerminalBlocks
Output
Breaker
TB7
TB2
L1 L2
Output Terminal Block wire
range: (1) #14 - #2 AWG
per connection
Output Wiring
Access Area
Output Conduit
Landing Area
Input Conduit
Landing Area
8-12 kVA Rear View
G

NOTES

Weight, including load modules, about 100 lbs.
Attach brackets to wall as shown using customer-
supplied 1/4” hex head lag screw or equivalent
hardware.
Options: 5’ UPS to CD Power Cable, 5’ Power
Management Power Cable, Wall Mount Bracket,
and Load Modules.
Refer to NEC Article 250 and local codes for proper
wire sizing and grounding practices.

Configurable Distribution may be used on all

Liebert UPStation S™ units up to 12 kVA.