Liebert iCOM Control—Firmware Version XP1.00.010.STD
56
Humidity Sensor B—Adjusts the humidity reading from the actual remote sensor designated as
Sensor B to compensate for any error of the sensor or to match other sensors in the room.
Calibrated Humidity Sensor B—Displays the adjusted humidity value of the remote CAN Temp
Humidity sensor designated as Sensor B. This value is the actual sensor reading plus or minus the
offset Humidity Sensor B.
Figure 61 Sensor Calibration/Setup screen, page 2 of 3
Supply Refrigerant Sensor—Adjusts the temperature reading from the actual supply refrigerant
sensor to compensate for any error of the sensor.
Calibrated Supply Refrigerant Sensor—Displays the adjusted temperature value of the supply
refrigerant sensor. This value is the actual sensor reading plus or minus the offset Supply Refrigerant
Sensor.
Supply Chilled Water Sensor—Adjusts the temperature reading from the actual supply chilled
water sensor to compensate for any error of the sensor.
Calibrated Chilled Water Sensor—Displays the adjusted temperature value of the supply chilled
water sensor. This value is the actual sensor reading plus or minus the offset Supply Chilled Water
Sensor.
Figure 62 Sensor Calibration/Setup screen, page 3 of 3
SENSOR CALIBRATION/SETUP (page 2 of 3) UNIT 01
to confirm
for next/prev ious unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0 )
Supply Ref rigerant Sensor
Calibrated Suppl y Refrigerant Sens or
Supply Chil led Water Sensor
Calibrated Suppl y Chilled Wat er Sensor
S612
S613
S614
S615
S616
S617
S618
S619
S620
S621
S622
????
+0.0° F
58.5°F
+0.0° F
60.1°F
SENSOR CALIBRATION/SETUP (page 3 of 3) UNIT 01
PASSW ORD (Actual Level 0 )
Supply Ref rigerant Sensor 0%
Supply Ref rigerant Sensor 100%
S623
S624
S625
S626
S627
S628
S629
S630
S631
S632
S633
????
30.0°F
90.0°F
to confirm
for next/prev ious unit
then
to select parameter
to change parameter