Troubleshooting

7.0TROUBLESHOOTING

Table 14

Troubleshooting the Liebert XDP

 

 

 

 

Symptom

Possible Cause

Check or Remedy

 

 

No main power

Check L1, L2 and L3 for rated voltage.

 

 

Loose electrical connections

Tighten connections.

Pump Will Not Energize

Overloads tripped

Allow pump to cool. Check amp draw.

 

 

 

 

 

 

Tripped circuit breaker

Check circuit breaker to pump(s).

 

 

 

 

 

 

Incorrect phase wiring

See Table 13.

 

 

No chilled water

Check and verify that there is supply chilled water to the

 

 

Liebert XDP.

 

 

 

 

 

Isolation valve(s) on pump suction

Open all isolation valves completely during normal operation.

 

 

and/or discharge is closed.

 

 

 

Pump Will Not Start or

Supply chilled water is too high

Check and verify that the chilled water temperature setpoint is

Run

 

at 50°F (10°C) or lower and that there is flow on the chilled

 

 

 

water side.

 

 

Liebert XD cooling modules are Off

Check Liebert XD cooling modules to make sure that they are

 

 

On prior to starting the Liebert XDP.

 

 

 

 

 

 

Check alarm(s) history on Liebert XDP. The Liebert XDP was

 

 

Low Refrigerant Temperature

operating below the dew point for a significant amount of time.

 

 

Check humidity in conditioned space, lower humidity if

 

 

(high dew point)

necessary to allow Liebert XDP to operate at a lower

 

 

 

temperature. (Disconnect must be switched to Off then back

 

 

 

On to allow Liebert XDP to reset itself).

 

 

Pressure switch not making contact

Check both differential pressure settings. If not within 6 psi, ±1

 

 

psi (41kPa, ±7kPa; 0.41 bars, ±0.07bars) then manually

 

 

 

change accordingly.

 

 

Not enough charge

See 5.1 - Checklist for Liebert XDP Startup.

 

 

Chilled water valve not closing

Wait at least 10 minutes before calibrating. Access the

Pump Will Not Start

Advanced Menu>Factory Settings>Calibrate Actuator.

completely.

 

 

Contact Liebert Services for assistance, 1-800-543-2778.

 

 

 

 

 

 

 

 

 

Cavitation due to vapor in pump

Check for adequate charge in system, refer to the User's

 

 

Manual. 5.1 - Checklist for Liebert XDP Startup

Pump Noisy

 

 

 

Worn motor bearings

Replace pump

 

 

 

 

Pump is rotating in reverse

See Table 13.

 

 

 

1. Check humidity of the room along with the location of

 

 

 

remote sensors. Make sure that the sensors are not in a cold

 

 

Low refrigerant temperature

area where there is insufficient air flow for accurate,

 

 

representative readings.

 

 

 

 

 

 

2. Chilled Water temperature is too cold.

 

 

 

3. Load is too light.

 

 

Loss of power

When power is restored, the Liebert XDP will automatically

Liebert XDP (Pump)

restart.

 

Suddenly Stops

Clogged filter dryer and/or impeller

Clean out debris

 

 

 

 

 

 

Leak in system - loss of charge

Check the entire system for leaks with a refrigerant sniffer.

 

 

Repair as necessary.

 

 

 

 

 

Low chilled water temperature alarm

Check supply chilled water temperature.

 

 

and loss of flow Pump X alarm

 

 

 

 

 

Supply refrigerant sensor failure

Check wiring.

 

 

alarm

Call service.

Clogged Filter Dryer

Debris or other contaminants in

Replace.

and/or Impeller

refrigerant

 

Pipe Rattle

 

Loose pipe connections

Check pipe connections.

 

 

Motor operates but valve won't open

Check linkage for adjustment and be sure that it is tight on the

 

 

valve.

 

 

 

Chilled Water Valve Not

No 24 VAC power to motor

Check for 24 VAC between P52-1 and P52-4.

 

 

No signal from control

Check 24 VAC at P22-1 (close) or P22-3 (open).

Working

 

 

 

 

 

Unplug P22 from the board. Jumper P22-5 to P52-4 for

 

 

 

 

 

Motor not operating

grounding, then jumper P22-1 to P52-1 to drive close. Remove

 

 

jumper to close and then jumper P22-3 to P52-1 to drive open.

 

 

 

 

 

 

If motor fails to work, replace it.

 

 

 

 

69

Page 75
Image 75
Liebert XDP160RM, XDP160RC, XDP160RA user manual Troubleshooting the Liebert XDP, Symptom Possible Cause Check or Remedy

XDP160RA, XDP160RC, XDP160RM specifications

The Liebert XDP series is an innovative line of uninterruptible power supplies (UPS) designed to safeguard critical IT equipment and ensure reliability in demanding environments. The XDP160RM, XDP160RC, and XDP160RA models are distinguished by their robust features and advanced technologies, making them ideal for data centers, server rooms, and telecommunications.

One of the standout features of the Liebert XDP series is its high power density. The XDP160RM, XDP160RC, and XDP160RA models provide 160 kVA of power in a compact design, occupying minimal floor space. This efficient design maximizes data center performance without compromising on reliability.

All three models utilize advanced digital signal processing (DSP) technology that enhances system performance and efficiency. The DSP technology ensures high efficiency rates, often exceeding 95% in online mode. This not only reduces energy costs but also minimizes heat output, contributing to a more sustainable operational environment.

The Liebert XDP series is equipped with multiple output configurations, allowing for versatile installation options. The modular architecture of the UPS systems allows for easy scalability to meet future power demands without the need for complete system replacement. This flexibility is crucial for businesses expecting growth or changes in IT infrastructure.

Another important aspect of the XDP160RM, XDP160RC, and XDP160RA is their advanced battery management systems, which optimize battery performance and longevity. The integrated smart battery charging technology prevents overcharging and extends battery life, ensuring that the UPS is always ready during power interruptions.

Additionally, the systems are designed with user-friendly interfaces that facilitate ease of monitoring and management. With real-time data on power usage, battery status, and overall system health, IT administrators can quickly address any issues that arise. The monitoring capabilities extend to remote access, enabling users to manage the UPS systems from virtually anywhere.

The Liebert XDP series also incorporates enhanced safety features, including fault detection and automated alerts, which further bolster reliability. With a strong commitment to maintaining uptime and safeguarding critical operations, the XDP models are a wise investment for any organization reliant on continuous power availability.

In conclusion, the Liebert XDP160RM, XDP160RC, and XDP160RA UPS systems are engineered to deliver exceptional power protection through high efficiency, advanced technologies, and user-friendly management features. These models are positioned to meet the rigorous demands of modern IT environments, ensuring that businesses can maintain operations without interruption.