IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important safety instructions that should be followed during the installation and maintenance of the Liebert XDP. Read this manual thoroughly before attempting to install or operate this unit.

Only qualified personnel should move, install or service this equipment.

Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit and in this manual. Follow all operating and user instructions.

Follow all local codes.

! WARNING

Risk of arc flash and electric shock. Can cause property damage, injury or death.

Disconnect all local and remote electric power supplies and wear protective equipment per NFPA 70E before working within electric control enclosure. Failure to comply can cause serious injury or death.

Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.

Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power.

The Liebert iCOM microprocessor does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of Liebert iCOM control.

The line side of the disconnect switch on the front of the unit contains live high-voltage.

The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic.

Follow all local codes.

! WARNING

Risk of unit falling over. Can cause property damage, injury or death.

The XDP is top-heavy. Use extreme caution and care when moving and installing this unit.

! CAUTION

Risk of piping and component rupture. Can cause injury or equipment damage.

System is pressurized. Relieve pressure through access valve before working on unit.Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do not close valves without following recommended procedures for repair, maintenance and replacement of components. Install pressure relief valves in field piping that may become isolated by service valves. System is pressurized. Relieve pressure through access valve before working on unit

NOTE

This document is intended to be used together with site specific documentation and documentation for other parts of the system (heat rejection devices and cooling modules).

NOTE

Before any action that could cause a disturbance in the XD system’s cooling function is begun, the facility manager MUST be informed. In addition, after the action is taken and the work is finished, the facility manager MUST be informed.

NOTICE

Risk of leaking chilled water lines. Can cause equipment and building damage.

Lines and joints must be inspected regularly. Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment. Do not locate unit directly above any equipment that could sustain water damage. Emerson Network Power recommends installing monitored leak detection equipment for the unit and supply and return lines.

1

Page 7
Image 7
Liebert XDP160RC, XDP160RM, XDP160RA user manual Important Safety Instructions

XDP160RA, XDP160RC, XDP160RM specifications

The Liebert XDP series is an innovative line of uninterruptible power supplies (UPS) designed to safeguard critical IT equipment and ensure reliability in demanding environments. The XDP160RM, XDP160RC, and XDP160RA models are distinguished by their robust features and advanced technologies, making them ideal for data centers, server rooms, and telecommunications.

One of the standout features of the Liebert XDP series is its high power density. The XDP160RM, XDP160RC, and XDP160RA models provide 160 kVA of power in a compact design, occupying minimal floor space. This efficient design maximizes data center performance without compromising on reliability.

All three models utilize advanced digital signal processing (DSP) technology that enhances system performance and efficiency. The DSP technology ensures high efficiency rates, often exceeding 95% in online mode. This not only reduces energy costs but also minimizes heat output, contributing to a more sustainable operational environment.

The Liebert XDP series is equipped with multiple output configurations, allowing for versatile installation options. The modular architecture of the UPS systems allows for easy scalability to meet future power demands without the need for complete system replacement. This flexibility is crucial for businesses expecting growth or changes in IT infrastructure.

Another important aspect of the XDP160RM, XDP160RC, and XDP160RA is their advanced battery management systems, which optimize battery performance and longevity. The integrated smart battery charging technology prevents overcharging and extends battery life, ensuring that the UPS is always ready during power interruptions.

Additionally, the systems are designed with user-friendly interfaces that facilitate ease of monitoring and management. With real-time data on power usage, battery status, and overall system health, IT administrators can quickly address any issues that arise. The monitoring capabilities extend to remote access, enabling users to manage the UPS systems from virtually anywhere.

The Liebert XDP series also incorporates enhanced safety features, including fault detection and automated alerts, which further bolster reliability. With a strong commitment to maintaining uptime and safeguarding critical operations, the XDP models are a wise investment for any organization reliant on continuous power availability.

In conclusion, the Liebert XDP160RM, XDP160RC, and XDP160RA UPS systems are engineered to deliver exceptional power protection through high efficiency, advanced technologies, and user-friendly management features. These models are positioned to meet the rigorous demands of modern IT environments, ensuring that businesses can maintain operations without interruption.