Liebert iCOM Control—Firmware Version XP1.00.010.STD

Figure 58 Set Alarms screens, pages 5 and 6

 

 

 

 

 

 

 

 

 

 

 

S259 PASSWORD (Actual Level 0)

????

 

 

S250

 

DELAY EN-DIS TYPE

 

 

S251

 

 

 

 

S252

 

 

 

 

S253

 

 

 

 

S254

 

 

 

 

S255

 

 

 

 

S256

 

 

 

 

S257

 

 

 

 

S258

 

 

 

 

S259

 

 

 

 

S260

 

 

 

 

S261

 

 

 

 

 

 

 

 

for next/previous unit

to select parameter

 

 

then

to change parameter

to confirm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S262 PASSWORD (Actual Level 0)

????

 

 

S263

 

DELAY EN-DIS TYPE

 

 

S264

 

 

 

 

S265

 

 

 

 

S266

 

 

 

 

S267

 

 

 

 

S268

 

 

 

 

S269

 

 

 

 

S270

 

 

 

 

S271

 

 

 

 

S272

 

 

 

 

S273

 

 

 

 

S274

 

 

 

 

 

 

 

 

for next/previous unit

to select parameter

 

 

then

to change parameter

to confirm

 

 

 

 

 

 

Pages 5 and 6 apply to the Liebert XDC only. No Liebert XDP parameters are present.

Figure 59 Set Alarms screen, page 7 of 7

 

 

 

 

 

 

 

 

 

 

S275

PASSWORD (Actual Level 0)

 

????

S276

 

 

DELAY

EN-DIS TYPE

S277

 

 

 

 

S278

CONDENSATION DETECTED

3

ENABLE ALM

S279

FAN FAILURE

3

ENABLE ALM

S280

CUSTOMER INPUT 1

5

ENABLE ALM

S281

SMOKE DETECTED

5

ENABLE ALM

S282

WATER UNDER FLOOR

5

ENABLE ALM

S283

UNIT X DISCONNECTED

 

ENABLE WRN

S284

WORKING HRS EXCEEDED

 

ENABLE WRN

S285

CALL SERVICE

5

ENABLE ALM

S286

LOSS OF POWER

 

ENABLE WRN

S287

 

 

 

 

 

 

for next/previous unit

to select parameter

then

to change parameter

 

to confirm

CONDENSATION DETECTED—Enables or disables the Condensation Detected event, which occurs when water is detected at a Liebert XD cooling module. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

FAN FAILURE—Enables or disables the Fan Failure event, which occurs when a fan failure occurs at a Liebert XD cooling module. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

CUSTOMER INPUT 1—Enables or disables the Customer Input 1 event, which occurs when 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

SMOKE DETECTED—Enables or disables the Smoke Detected event, which occurs when the Customer Input 1 is configured for “Smoke Detected” and 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

NOTE

This is not a room smoke detector and is not intended to replace external smoke detectors.

54

Page 60
Image 60
Liebert XDP160RM, XDP160RC, XDP160RA Condensation Detected Enable ALM, FAN Failure Enable ALM, Customer Input Enable ALM

XDP160RA, XDP160RC, XDP160RM specifications

The Liebert XDP series is an innovative line of uninterruptible power supplies (UPS) designed to safeguard critical IT equipment and ensure reliability in demanding environments. The XDP160RM, XDP160RC, and XDP160RA models are distinguished by their robust features and advanced technologies, making them ideal for data centers, server rooms, and telecommunications.

One of the standout features of the Liebert XDP series is its high power density. The XDP160RM, XDP160RC, and XDP160RA models provide 160 kVA of power in a compact design, occupying minimal floor space. This efficient design maximizes data center performance without compromising on reliability.

All three models utilize advanced digital signal processing (DSP) technology that enhances system performance and efficiency. The DSP technology ensures high efficiency rates, often exceeding 95% in online mode. This not only reduces energy costs but also minimizes heat output, contributing to a more sustainable operational environment.

The Liebert XDP series is equipped with multiple output configurations, allowing for versatile installation options. The modular architecture of the UPS systems allows for easy scalability to meet future power demands without the need for complete system replacement. This flexibility is crucial for businesses expecting growth or changes in IT infrastructure.

Another important aspect of the XDP160RM, XDP160RC, and XDP160RA is their advanced battery management systems, which optimize battery performance and longevity. The integrated smart battery charging technology prevents overcharging and extends battery life, ensuring that the UPS is always ready during power interruptions.

Additionally, the systems are designed with user-friendly interfaces that facilitate ease of monitoring and management. With real-time data on power usage, battery status, and overall system health, IT administrators can quickly address any issues that arise. The monitoring capabilities extend to remote access, enabling users to manage the UPS systems from virtually anywhere.

The Liebert XDP series also incorporates enhanced safety features, including fault detection and automated alerts, which further bolster reliability. With a strong commitment to maintaining uptime and safeguarding critical operations, the XDP models are a wise investment for any organization reliant on continuous power availability.

In conclusion, the Liebert XDP160RM, XDP160RC, and XDP160RA UPS systems are engineered to deliver exceptional power protection through high efficiency, advanced technologies, and user-friendly management features. These models are positioned to meet the rigorous demands of modern IT environments, ensuring that businesses can maintain operations without interruption.