Simplified Installation

Example diagram only - duct configuration may change depending on model

Simplified Installation

Option 1

(Return/Return Method)

Note: Option 1 is the preferred / recommended method when doing a simplified installation.

DIRECT CONNECTION of both the HRV/ERV SUPPLY AIR STREAM and

EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN

RETURN AIR

Outdoors

40" (1m) MINIMUM

3’ min.

recommended

Cool Air

Return

Forced Air

Furnace

NOTES:

1.Furnace blower may be required to operate when ventilation from HRV/ERV is required. The furnace should be set to run continuously or interlocked with HRV/ERV.

2.A minimum separation of 40 inches (1 m) is required between the two direct connections.

3.The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.

4.Weatherhood arrangement is for drawing purposes only. Six feet (2 m) minimum separation required. Eighteen inches (460 mm) above grade minimum.

5.Due to the differences in pressure between the HRV/ERV and the equipment it is being connected to, the HRV/ERV's airflow must be confirmed on site, using the balancing procedure found in the installation manual.

*Unit is normally balanced on HIGH speed with furnace blower ON.

22