Lifebreath 200ERVD, 200MAX, 95MAX Simplified Installation, Option, Forced Air Furnace, Outdoors

Models: MAXTOP 195DCS 200ERVD 200ERV 300DCS 155MAX 95MAX 200MAX

1 32
Download 32 pages 16.73 Kb
Page 23
Image 23
Manual background

Example diagram only - duct configuration may change depending on model

Simplified Installation

Option 2

(Supply/Return Method)

It may be necessary to form an elbow in the supply side ducting as shown

DIRECT CONNECTION of both the HRV/ERV SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE

RETURN AIR

3’ min.

recommended

Outdoors

Cool Air

Return

NOTES:

1.Furnace blower may be required to operate when ventilation from HRV/ERV is required. The furnace should be set to run continuously or interlocked with HRV/ERV.

2.The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.

3.Weatherhood arrangement is for drawing purposes only. Six feet (2 m) minimum separation required. Eighteen inches (460 mm) above grade minimum.

4.Due to the differences in pressure between the HRV/ERV and the equipment it is being connected to, the HRV/ERV's airflow must be confirmed on site, using the balancing procedure found in the installation manual.

23

3’ min.

recommended

Forced Air

Furnace

Page 23
Image 23
Lifebreath 200ERVD, 200MAX, 95MAX, 155MAX, MAXTOP, 300DCS, 195DCS Simplified Installation, Option, Forced Air Furnace, Outdoors