ENGINEERING DATA

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE

The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.

MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, .8 Amps.

FILTERS - Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV - Four threaded inserts at corners of the cabinet designed to accept PVC reinforced polyester straps that are supplied with the unit.

DEFROST - Recirculating defrost system.

CASE - Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.

CONTROLS - ControlAir 15

WEIGHT 52 lbs. (23.6 kg) SHIPPING WEIGHT 56 lbs. (25.4 kg)

Model 95MAX

PERFORMANCE

HVI CERTIFIED

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

 

cfm

L/s

@ 0.1” (25

Pa)

89

(42)

@ 0.2” (50

Pa)

78

(37)

@ 0.3”

(75

Pa)

64

(30)

@ 0.4”

(100 Pa)

36

(17)

Maximum Temperature Recovery

74%

 

 

Sensible Effectiveness

80%

@ 64 cfm (30 L/s) (CSA C439M)

Sensible Efficiency

 

 

@ 64 cfm (30 L/s)

32˚F (0˚C)

75%

Sensible Efficiency

 

 

@ 64 cfm (30 L/s)

-13˚F (-25˚C)

75%

 

 

 

VAC @ 60HZ

 

120

WATTS / Low speed

35

WATTS / High speed

136

Amp rating

 

0.8

 

 

 

DIMENSIONS 95MAX

inches (mm)

 

 

 

 

 

 

 

 

18.5"

 

 

Hanging

 

 

 

(470 mm)

 

 

 

 

 

 

 

straps (4)

 

 

 

 

 

knockout for

 

 

 

 

 

 

Threaded

 

 

 

 

side mounting of

 

 

 

 

 

 

inserts (4)

 

 

 

 

EXHAUST return port

 

 

 

 

 

 

at corners

 

 

 

 

6" round collar

 

 

 

 

 

 

 

 

 

 

 

converted to oval

 

 

18.5"

 

 

 

 

 

 

 

 

 

 

 

 

(470 mm)

 

 

 

 

 

 

EXHAUST

 

mm)(622

 

 

 

SUPPLY

Stale Air

 

 

 

 

to outside

24.5"

 

 

 

Fresh air

Core

 

 

EXHAUST

 

 

Removably

 

 

from outside

5" round collar

 

 

Heat Recovery

 

 

5" round collar

 

 

 

 

 

 

 

Return air

 

 

 

 

 

SUPPLY

from building

 

 

 

minimum

 

Fresh air

Choice of port location

 

 

 

 

to building

 

 

 

18 inches (459 mm)

 

 

 

 

 

6" round

Knockouts on top and

 

 

 

required for

 

 

 

 

 

(conv. to oval)

side of unit (use 1 only)

 

 

 

service access

 

 

 

Drain Pan

 

collar

6" round (conv. to oval)

 

 

 

 

 

 

 

 

 

 

collar supplied

 

 

Drain spout

 

16"

 

 

 

 

 

 

 

 

 

FRONT

 

SIDE

(406 mm)

 

TOP

 

 

 

 

OPTIONS

 

 

 

 

 

99-104Digital Electronic Timer - 20/40/60 min.

99-105Programmable Ventilation Control (PVC)

includes Programmable Time Clock, Dehumidistat

and Air Sentry™

99-109 Air Sentry™ Air Quality Monitor designed to accept remotely mounted Control Pad

99-250 Ventilation Dehumidistat - Dehumidistat designed to accept remotely mounted Control Pad

DATE: __________________________

99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw,

6” (150 mm)

99-186 Weatherhoods, Two - 5” (125 mm) c/w 1/4” (6 mm) mesh screen

All units conform to CSA and UL standards.

WARRANTY

Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.

 

511 McCormick Blvd.

PROJECT: ________________________________________

London, Ontario N5W 4C8

Ph: (519) 457-1904

 

 

Fx: (519) 457-1676

MECHANICAL CONTRACTOR: ________________________________

Email: nutech@lifebreath.com

Website: www.lifebreath.com

5

TI-113-NE

 

0103

Page 5
Image 5
Lifebreath 155MAX, 200MAX Model 95MAX, DIMENSIONS 95MAX, Engineering Data, Performance, Side, Front, Options, inches mm