GE GFK-1541B manual Major Error Codes, Error Status Major Error Description

Models: GFK-1541B

1 240
Download 240 pages 31.35 Kb
Page 104
Image 104

3

3.A status code of 1 in the low byte and 0 in the high byte indicates that the request was successful. All other non-zero values indicate errors. Refer to the tables below for a complete listing of major and minor error codes.

The following tables list the error codes that are reported in the COMMREQ Status word after the execution of a COMMREQ function. These codes also may appear in Word 1 of the Detailed Channel Status words.

Major Error Codes

Error Status

Major Error Description

Hexadecimal

 

01H

Successful Completion. (This is the expected completion value in the

 

COMMREQ Status word.)

02H

Insufficient Privilege at server PLC. For a Series 90-70 server PLC, the minor error

 

code contains the privilege level required for the service request.

04H

Protocol Sequence Error. The server CPU has received a message that is out of order.

 

Call GE Fanuc Automation - NA for assistance.

05H

Service Request Error at server PLC. The minor error code contains the specific error

 

code. See the following table of Minor Error codes.

06H

Illegal Mailbox Type at server PLC. Service request mailbox type is either undefined

 

or unexpected. Call GE Fanuc Automation - NA for assistance.

07H

The server PLC CPU’s Service Request Queue is full, usually due to heavy CPU

 

loading. The client should retry later. It is recommended that the client wait a

 

minimum of 10 milliseconds before sending another service request.

0BH

Illegal Service Request. The requested service is either not defined or not supported

 

at the server PLC. (This value is returned in lieu of the actual service request error

 

(01H), to avoid confusion with the normal successful COMMREQ completion.) Call

 

GE Fanuc Automation - NA for assistance.

11H

SRTP Error Codes at server. An error was detected at the SRTP server. See the

 

following table of Minor Error codes.

82H

Insufficient Privilege at client PLC. For the Series 90-70 PLC, the minor error code

 

contains the privilege level required for the service request.

84H

Protocol Sequence Error. The CPU has received a message that is out

 

of order. Call GE Fanuc Automation - NA for assistance.

85H

Service Request Error at the client PLC. The minor error code contains the specific

 

error code. See the following table of Minor Error codes.

86H

Illegal Mailbox Type. Service request mailbox type is either undefined or

 

unexpected. Call GE Fanuc Automation - NA for assistance.

87H

The client PLC CPU’s Service Request Queue is full. The client should retry later. It

 

is recommended that the client wait a minimum of 10 milliseconds before sending

 

another service request.

8BH

Illegal Service Request. The requested service is either not defined or not supported.

 

(This value is returned in lieu of the actual service request error (01H), to avoid

 

confusion with the normal successful COMMREQ completion.). Call GE Fanuc

 

Automation - NA for assistance.

90H

Client API error. See the following table of Minor Error codes.

GFK-1541B

Chapter 3 Programming Channel Commands

3-37

Page 104
Image 104
GE GFK-1541B manual Major Error Codes, Error Status Major Error Description