Read Data from a Modbus/TCP Device (3003)

The Read Data from a Modbus/TCP Device COMMREQ requests a data transfer from a Modbus/TCP device to the PLC. The Read Data COMMREQ must reference an active Modbus/TCP channel previously established with the Open Modbus/TCP Client Connection

COMMREQ.

Registers, Coils or Exception Status data may be read from the remote Modbus/TCP device. The Modbus Function Code specifies the data type. Valid Function Codes for the Read Data COMMREQ are presented in the following table:

Function

Description

Base Address

Data Unit Size

Maximum Data

Code

 

 

 

Units

 

 

 

 

 

1

Read Coils

00001

Bit

2000

 

 

 

 

 

2

Read Input Discretes

10001

Bit

2000

 

 

 

 

 

3

Read Multiple

40001

Register

125

 

Registers

 

(16-bit Word)

 

 

 

 

 

 

4

Read Input Registers

30001

Register

125

 

 

 

(16-bit Word)

 

7

Read Exception

Not Applicable

Byte

Not Applicable

 

Status

 

 

 

 

 

 

 

 

An Address and Length specify the location of the data in the remote device and the number of data units to transfer. The Length is the number of Registers or Coils to transfer. Modbus Function Code 7, Read Exception Status does not require the address as the remove device retrieves the exception status from an internal location.

Coil data is always padded with zeros when less than an even multiple of 16 bits of coil data is returned to the PLC.

Data returned from the remote device is stored in the PLC data area specified in the Read Modbus/TCP Device COMMREQ. Data can be stored in any of the PLC data areas. Refer to page 4-14 for the list of data areas and identification codes for the PLC. Note that the first item referred to in each data area is item 1 not item 0.

The COMMREQ Status Word (CSR) indicates the success or failure of the Read Data COMMREQ. If the COMMREQ requests an invalid channel number or any other field is invalid the COMMREQ fails and the CSR is set to a non-zero value to identify the failure. See the section “Status Data” later in this document for detailed CSR failure codes.

GFK-1541B