2

Installing the CMM321 in the PLC

For general information about module and system installation, refer to GFK-0356, Series 90-30 Programmable Controller Installation Manual.

Equipment Required to Perform the Installation Procedures

Make sure you have the items listed below before you begin.

ƒA Series 90-30 PLC CPU baseplate, or any Series 90-30 baseplate and a Series 90-30 CPU with power supply.

ƒThe CMM321 requires CPU version 6.50 or higher for full functionality. CPU versions 5.03 to 6.04 permit Ethernet operation with only 1 SRTP server connection.

ƒThe CMM321 requires PLC power supply IC693PWR321 (Revision K or later), IC693PWR322, or IC693PWR330.

ƒPLC programming software: Logic Developer (all versions), Control Version 2.01 or higher, VersaProversion 1.0 or higher, or Logicmaster 90-30 version 6.01 or higher. (And a

compatible PC-compatible personal computer.)

ƒIf you are using the AAUI port instead of the 10Base-T port, you will need an Ethernet- compatible AAUI transceiver and Ethernet cables. (See Appendix B for more information on the ports and transceivers.) Optional

ƒAn IC693CBL316 serial cable for the Station Manager port on the Ethernet Interface (see Appendix B). Optional

ƒA terminal or IBM-compatible personal computer equipped with terminal emulation software. Optional

Notes

If your installation requires CE Mark compliance, please refer to GFK-1179, Installation Requirements for Conformance to Standards, shipped with the PLC programming software, for additional guidelines.

A CMM321 can be mounted on a CPU baseplate, an expansion baseplate, or a remote baseplate. However, due to power requirements, only two Ethernet Interface modules are permitted per baseplate using a standard power supply. Up to four Ethernet Interface modules are permitted per baseplate using a high capacity power supply.

2-6

TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual– May 2002

GFK-1541B

Page 19
Image 19