Command 3004, Example 3 – Set Multiple Registers

Write the four registers from Discrete Input Memory (%I40 to) address 40200 in the remote Modbus/TCP server. Return the COMMREQ Status word to %R10. Use channel 6, a channel previously opened with the Open Modbus/TCP Client Connection COMMREQ.

 

Dec

(Hex)

 

Word 1

00008

(0008)

Length of Channel command Data Block

Word 2

00000

(0000)

Always 0 (no-wait mode request)

Word 3

00008

(0008)

Memory type of CRS word (%R)

Word 4

00009

(0009)

CRS word address minus 1 (%R10)*

Word 5

00000

(0000)

Reserved

Word 6

00000

(0000)

Reserved

Word 7

03004 (0BBC)

Write to a Modbus/TCP Device

Word 8

00006

(0006)

Channel number (6)

Word 9

00016

(0010)

Modbus Function Code – Preset Multiple Registers

Word 10

00016

(0010)

PLC Memory Type

Word 11

00040

(0028)

PLC Starting Address

Word 12

00200

(00C8)

Address in the Remote Device

Word 13

00004

(0004)

Number of Registers in the Remote Device

Word 14

00001

(0001)

Unit Identifier

*Word 4 (CRS word address) is the only zero-based address in the Command Block. Only this value requires subtracting 1 from the intended address.

(Word 7) Channel Command Number: Word 7 identifies the COMMREQ as a Write Data to Modbus/TCP device.

(Word 8) Channel Number: Word 8 identifies the channel number previously allocated for communication with the remote Modbus/TCP server.

(Word 9) Modbus Function Code: Word 9 specifies Modbus Function Code 6, Preset Single Register.

(Word 10) Local PLC Memory Type: Words 10–11 specify the location in the local PLC from where the Ethernet Interface will get the data to be written to the remote PLC. Valid values for Word 10 are listed on page 4-14. The value 16 specifies Discrete Input Memory %I(byte mode).

(Word 11) Local PLC Starting Address: Word 11 determines the starting address in the local PLC from which the data is to be written. The value entered is the offset (1-based) from the beginning of PLC memory for the memory type and mode specified in Word 10. This offset will be either in bits, bytes, or words depending on the mode specified. Valid ranges of values depend on the PLC’s memory ranges.

(Word 12) Remote Device Address: Word 12 specifies the destination register in the remote Modbus/TCP device.

(Word 13) Number Registers in Remote Device: Words 13 specifies the quantity of registers to write to the remote device.

(Word 14) Unit Identifier: Default is 1. This field is typically used by Ethernet to Serial bridges to specify the address of a Modbus Slave on a multidrop link. The Modbus/TCP Unit Identifier is a special control code used in a Modbus/TCP message block. This value is 1 for most Modbus/TCP messages.