2

States of the Series 90-70 CMM742 TCP/IP Ethernet Interface



Ethernet Interface



Initializing 1



 (approx.10-20 seconds)

1The Ethernet Interface is initialized by

-Powering-up the PLC

-Storing a new configuration to the PLC with changes for the Ethernet Interface

-Pressing the Restart pushbutton

-Issuing a Station ManagerRESTART,LOAD, or MAINT command

-Internal System Error occurring when Interface is Operational

No  A

Diagnostics  Hardware

Pass? Failure



Yes

Load

Yes2

œ

B

2

Request or

 

 

 

œ

Software

 

Software

 

 

 

 

 

 

 

 

 

 

 

œ

Load

 

Corrupted?

 

 

 

 

 

 

 

œ

 

 

 

 

 

 

 

 

No

3

 

C

œWaiting for

 Configuration from

 

 

 

 

 

4



 

PLC CPU

 

 

 

 

 

 

 

 

 

 

 

 



 

(max. 2 minutes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

Done

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes3

œ

D

 

 

IP address =

 

 

 

 

 

 

 

 

 

 

 

 

 

 

z/ / Waiting for

 

 

 

0.0.0.0

 

 

 

 



IP Address

 

 

 

 

 

 

 

 

 

œ

 

 

 

 

 

No

IP Address Received 4

 

 

 

 

 

 

 

 

 

 

 

Maintenance

Yes

5

œ

E

 

 

 

 

 

Request or

 

 

 

 

z/ /

Maintenance

 

 

 

 

 

 

œ

 

 

 

 

 

 

 

 

Fatal System

 

 

 

 

 

 

 

Error?

 

 

 

 

z/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

Maintenance

 

 

 

 

 

- Client and server capability disabled

 

 

 

 

 

 

 

 

 

 

- Uses default Advanced Parameters

z

 

 

F

- Permits changes to Advanced Parameters

 

 

 

 

 

 

 

 

z/

/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operational

z/

Operational

-Full support for client and server capability

-Uses user defined Advanced Parameters

Software Load Caused by

-Restart pushbutton pushed until bottom LED turns ON

-Station ManagerLOAD command issued

-Detection of corrupt software

Waiting for IP Address Caused by

-Not configuring Interface using configuration software

-Configuring Interface with IP address = 0.0.0.0

-New CPU with no configuration

-CPU failure to communicate with Interface

Continue to Maintenance or Operational Caused by

-IP address received from network BOOTP server

-IP address entered byBOOTP Station Manager command

Maintenance Request Caused by

-Restart pushbutton pushed until bottom two LEDs turn ON

-Station ManagerMAINT command issued

-Fatal System Error while in Operational State forced a restart

Symbols

The LEDs are labeled from top to bottom as follows:

MODULE OK

LAN ONLINE SERIAL ACTIVE STATUS

The symbols used for the LEDs are defined as follows:

= OFF

z= ON

œ= Slow Blink; multiple slow blining LEDs blink in unison

= Fast Blink

= Traffic (blinks when there is traffic on the line) The process symbols are defined as follows:

= Temporary condition; requires no intervention

= Decision point during power-up

= Interface State; normally the Interface remains in a State unless there is user intervention