States of the Series 90-30 CPU364 with Embedded TCP/IP Ethernet Interface

Ethernet Interface

Initializing1

(approx. 2-6 seconds)

1 The Ethernet Interface is initialized by

-Powering-up the PLC

-Storing a new configuration to the PLC with changes for the Ethernet Interface

-Pressing the Restart pushbutton

-Issuing a Station Manager RESTART, LOAD, or MAINT command

-Internal System Error occurring when Interface is Operational

 

 

 

No



A

 

 

 

 

 

 

 

Diagnostics

 

 

 

 Hardware

 

 

 

 

 

 

 

Pass?

 

 

 



Failure

 

 

 

Yes

Yes 2

 

B

2

 

 

 

 

Load

œ

 

Request or

 

Software

 

 

 

œ Software

 

 

 

 

 

 

 

Corrupted?

 

 

 

œ

Load

 

 

 

No

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

œ

C

 

 

 

 

 

 

Waiting for

 

 

 

 

 

4



Configuration

 

 

 

 

 

from PLC CPU (max. 2 seconds)

 

 

5

 

Done

 

 

 

 

 

Yes 3

œ

D

IP address =

Waiting for

 

 

 

 

z/ /

0.0.0.0

 

 

 

 

IP Address

 

 

 

 

œ

 

 

 

 

 

 

 

 

 

 

No

 

 

 

IP Address 4

 

 

 

 

 

 

 

 

 

 

 

 

 

Received

 

Maintenance

 

Yes 5

œ

E

 

 

Request or

 

 

 

 

z/ / Maintenance

 

 

 

 

Fatal

System

 

 

 

 

z/

 

Error?

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

Maintenance

 

 

 

 

 

 

 

- Client and server capability disabled

 

 

 

 

 

 

- Uses default Advanced Parameters

z

F

 

 

 

- Permits changes to Advanced Parameters

 

 

 

 

 

 

z/ / Operational

 

 

z/

 

 

 

 

 

 

 

 

Operational

-Full support for client and server capability

-Uses user defined Advanced Parameters

Software Load Caused by

-Restart pushbutton pushed until bottom LED turns ON

-Station Manager LOAD command issued

-Detection of corrupt software

Waiting for IP Address Caused by

-Not configuring Interface using configuration software

-Configuring Interface with IP address = 0.0.0.0

-New CPU with no configuration

-CPU failure to communicate with Interface

Continue to Maintenance or Operational Caused by

-IP address received from network BOOTP server

-IP address entered by BOOTP Station Manager command

Maintenance Request Caused by

-Restart pushbutton pushed until bottom two LEDs turn ON

-Station Manager MAINT command issued

-Fatal System Error while in Operational State forced a restart

Symbols

The LEDs are labeled from top to bottom as follows:

EOK

LAN

STAT

The symbols used for the LEDs are defined as follows:

= OFF

z= ON

œ= Slow Blink; multiple slow blinking LEDs blink in unison

= Fast Blink

= Traffic (blinks when there is traffic on the line) The process symbols are defined as follows:

= Temporary condition; requires no intervention

= Decision point during power-up

=Interface State; normally the Interface remains in a State unless there is user intervention