4

Minor Error Codes for Major Error Code 91H (Remote Server Device Error Codes)

Error Status

Error Description

(Hexadecimal)

 

0191H

Illegal Function. The function code received in the query is not an

 

allowable action for the server. This may be because the function

 

code is only applicable to newer controllers, and was not

 

implemented in the unit selected. It could also indicate that the

 

server is in the wrong state to process a request of this type, for

 

example because it was un-configured and is being asked to return

 

register status.

 

 

0291H

Illegal Data Address. The data address received in the query is not

 

an allowable address for the server. More specifically, the

 

combination of reference number and transfer length is invalid.

 

 

0691H

The server’s Service Request Queue is full, or the EEthernet

 

Interface received a Modbus Exception Code 06 SLAVE DEVICE

 

BUSY.

 

 

0791H

An internal server error occurred while attempting to process a Modbus request. This corresponds to the Modbus exception 07

NEGATIVE ACKNOWLEDGE

Note: If using a Modbus/TCP Server other than the IC693CMM321 and receive an error of the form xx91H that is not listed in this table, please refer to the documetation provided with the specific server for details on the meaning of the error.

GFK-1541B

Chapter 4 Programming Modbus/TCP Channel Commands

4-25