4

Description of the Status Data

The errors and status reported in each type of status data are described below.

FT Output of the COMMREQ Function Block

The FT Output passes power upon the following errors:

ƒInvalid rack/slot specified. The module at this rack/slot is unable to receive a COMMREQ.

ƒInvalid Task ID.

ƒInvalid Data Block length (zero or greater than 128).

ƒToo many simultaneous active COMMREQs (overloading either the PLC CPU or the Ethernet Interface).

LAN Interface Status (LIS) Bits

The status bits occupy a single block of memory. The location of this block is specified during configuration of the Ethernet Interface. The first 16 bits of the block are the LAN Interface Status (LIS) bits. The next 64 bits are the Channel Status bits (2 for each channel).

Status Bits

Brief Description

 

 

1–7

Reserved

 

 

8

AAUI (90-30) fuse blown

 

 

9

Any SRTP Channel Error

 

 

10–12

Reserved

 

 

13

LAN OK

 

 

14

Resource problem

 

 

15

Reserved

 

 

16

LAN Interface OK

 

 

17

Connection Open - Channel 1

 

 

18

Reserved

 

 

...

...

 

 

47

Connection Open - Channel 16

 

 

48

Reserved

 

 

49 –80

Reserved for 90-30

 

 

Note

Unless the “LAN Interface OK” bit is set (Status Bit 16), the other status bits are invalid.

GFK-1541B

Chapter 4 Programming Modbus/TCP Channel Commands

4-21

Page 136
Image 136
GE GFK-1541B manual Status Bits Brief Description, Lan Ok