Installing the CPU364 in the PLC
For general information about module and system installation, refer to
Equipment Required to Perform the Installation Procedures
Make sure you have the items listed below before you begin.
A Series
PLC programming software: Logic Developer (all versions), Control Version 2.01 or higher, VersaPro version 1.0 or higher, or Logicmaster
Ethernet cables and, if using the AAUI port, an
A serial cable for the Station Manager port on the Ethernet Interface (see Appendix B).
Optional
A terminal or
Note: If your installation requires CE Mark compliance, please refer to
CPU364 Installation
Use the following instructions as a guide when inserting a module into a slot in a baseplate. These instructions assume that the power supply on the baseplate is to your left.
Warning
Do not insert or remove modules with power applied. This could cause the PLC to Stop, damage the module, or result in personal injury.
1. Be sure the Series
2. Align the module with the CPU’s base slot (slot 1) and connector. Tilt the module upwards so that the top rear hook of the module engages the slot on baseplate.
3. Swing the module downward until the connectors mate and the
4. Visually inspect the module to be sure that it is properly seated.
5. Connect one of the Ethernet ports on the Ethernet Interface to the network. If you are using an external transceiver, connect the transceiver cable to the
Caution
Do not connect or disconnect a transceiver cable to the AAUI port while power is applied to the PLC. This may blow the AAUI port fuse and/or cause permanent damage to the Ethernet Interface.
6. Restore power to the baseplate.
7. Use the PLC programming software or a Hand Held Programmer to make sure the PLC CPU is in Stop mode.
Chapter 2 Installation |