10.Use the SOSW Station Manager command to verify that all configuration parameters have been set to the proper values. A typical SOSW command is shown below:

* sosw

<<< Soft Switch Data >>>

IP Address

= 10.0.0.1

(TCP/IP values from

Soft Switches)

 

 

Subnet Mask

= 0.0.0.0

 

 

Gateway

= 0.0.0.0

 

 

Name Server

= 0.0.0.0

 

 

Port 1 (Station Manager):

Port 2 (S/W Loader):

Data Rate

= 9600

Data Rate

= 19200

Parity

= NONE

Parity

= ODD

Stop Bits

= 1

Stop Bits

= 1

Flow Control

= NONE

Flow Control

= NONE

TurnA Delay

= NONE

TurnA Delay

= NONE

Timeout

= LONG

Timeout

= LONG

Source of Soft Switches: Internal Backup

11.When all configuration parameters have been correctly entered, use the RESTART Station Manager command to restart the Ethernet Interface into normal operation.

The RESTART command is shown below:

=restart Restarting module

The Ethernet Interface is restarted into the Operational state. After approximately 20 seconds, another NODE output is automatically generated when the restart is complete. The NODE output should indicate the IP Address configured in Step 9, above. (The Subnet Mask, Gateway IP Address and Name Server IP Address can be displayed by the SOSW command, as described in Step 10, above.) The Ethernet Interface is now properly configured and ready for use.

Please proceed to the Installation chapter to verify proper operation of the Ethernet Interface with the new configuration data.

GFK-1541B

Appendix D Using the IC697CMM742 with PLC CPU Versions 4.12 - 5.50

D-5