Lincoln Series 1000, Series 1200 service manual Code

Models: Series 1000 Series 1200

1 112
Download 112 pages 35.42 Kb
Page 30
Image 30

Light#4 in 24VAC at terminal #6 of Johnson control valve or "24V" on Honeywell Control. Light#5 in 24VAC at terminal #1 of Johnson control valve or "PV" on Honeywell Control. Light#6 in 24VAC at terminal #3 of Johnson control valve or "MV" on Honeywell Control.

CODE:

All lights off - lights of main power, main fan off, air pressure switch out.

1 on 2 off 3 on 4 off 5 off 6 off

- Burner Motor Relay bad.

1 on 2 on

3 on 4 off 5 off 6 off

- Burner Motor Centrifugal Switch bad.

1 on 2 on

3 on 4 on 5 off 6 off

- Ignition Control bad.

1 on 2 on

3 on 4 on 5 on 6 off

- Pilot Shield missing or warped, Flame Sensor bad, Pilot

 

 

- Orifice plugged, or Gas Valve bad.

1 on 2 on 3 on 4 on 5 on 6 on

- Unit still not working Main Orifice plugged, Gas Valve bad,

 

 

- Temperature Control bad.

 

 

- However, Main Orifice would not be intermittent problem.

30

Impinger I -–1000 Series Service Manual - International

Page 30
Image 30
Lincoln Series 1000, Series 1200 service manual Code