A-6

INSTALLATION

A-6

PLUGS AND HAND HELD EQUIPMENT

For further protection against electric shock, any elec- trical equipment connected to the generator recepta- cles must use a three-blade, grounded type plug or an Underwriter’s Laboratories (UL) approved double insulated tool with a two blade plug.

WARNING

Never operate this machine with damaged or defective cords. All electrical equipment must be in safe operating condition.

------------------------------------------------------------------------

AUXILIARY POWER RECEPTACLES

The control panel of the OUTBACK™ 145 features three auxiliary power receptacles:

Two 20 amp,120 volt duplex (double outlet) receptacle.

A 50 amp, 240 volt single outlet receptacle.

See Figure A.1

Through these receptacles the machine can supply up to 4750 watts peak or 4250 watts continuous of sin- gle-phase 60 Hertz AC power. The machine output voltages meet UL standards and fall within ± 10% of the rated voltage.

PREMISES WIRING

The OUTBACK™ 145 is not recommended for premises wiring. The OUTBACK™ 145 does not have a combined 120/240 volt receptacle and cannot be connected to a premises.

The OUTBACK™ 145 is intended only for backup intermittent power.

Certain electrical devices cannot be provided by the OUTBACK™ 145 . Refer to table A . 2 for these devices.

CIRCUIT BREAKERS

Auxiliary power is protected by circuit breakers. When the machine is operated in high temperature environ- ments, the breakers may tend to trip at lower loads than normally.

CAUTION

NEVER BYPASS THE CIRCUIT BREAKERS. WITH- OUT OVERLOAD PROTECTION, THE UNIT COULD OVERHEAT AND/OR CAUSE DAMAGE TO THE

EQUIPMENT BEING USED.

------------------------------------------------------------------------

OUTBACK™ 145

¤

Page 13
Image 13
Lincoln Electric 145 manual Plugs and Hand Held Equipment, Auxiliary Power Receptacles, Premises Wiring, Circuit Breakers