B-8

 

OPERATION

 

 

B-8

 

TABLE B.4 Vantage Simultaneous Welding and Power Loads

 

 

 

 

 

 

 

Welding Output

 

Permissible Power Watts

 

Permissible Auxiliary

at NEMA Voltage

 

(Unity Power Factor)

 

Current in Amperes

(V=.04I + 20)

 

 

@ 120VAC * +/- 10%

 

@ 240 VAC +/- 10%

 

 

 

 

 

 

 

0-250A/30V

 

12,000

 

100**

 

50

350A/34V

 

8,100

 

68**

 

34

400A/36V

 

5,600

 

46

 

23

450A/38V

 

2,900

 

24

 

12

500A/40V

 

0

 

0

 

0

 

 

 

 

 

 

 

* Each duplex receptacle is limited to 20 amps.

**Not to exceed 50A per 120 VAC branch circuit when splitting the 240 VAC output.

TABLE B.5 Vantage Extension Cord Length Recommendations

Current

Voltage

Load

 

 

Maximum Allowable Cord Length in ft. (m) for Conductor Size

 

 

(Amps)

(Volts)

(Watts)

14 AWG

12 AWG

10 AWG

8 AWG

6 AWG

4 AWG

15

120

1800

30

(9)

40

(12)

75

(23)

125

(38)

175

(53)

300

(91)

15

240

3600

60

(18)

75

(23)

150

(46)

225

(69)

350

(107)

600

(183)

20

120

2400

 

 

30

(9)

50

(15)

88

(27)

138

(42)

225

(69)

20

240

4800

 

 

60

(18)

100

(30)

175

(53)

275

(84)

450

(137)

25

240

6000

 

 

 

 

90

(27)

150

(46)

225

(69)

250

(76)

30

240

7200

 

 

 

 

75

(23)

120

(37)

175

(53)

300

(91)

38

240

9000

 

 

 

 

 

 

100

(30)

150

(46)

250

(76)

50

240

12000

 

 

 

 

 

 

 

 

125

(38)

200

(61)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conductor size is based on maximum 2.0% voltage drop.