Lincoln Electric SVM148-B service manual Return

Models: SVM148-B

1 140
Download 140 pages 28.49 Kb
Page 43
Image 43

C-8

C-8

ACCESSORIES

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

CONNECTION OF THE K488 SG CONTROL MODULE AND K487 MAGNUM SPOOL GUN TO THE RANGER 300 (DLX ONLY) (SEE FIGURE C.6.)

1.Shut the welder off.

2.Connect the electrode cable from the SG Control Module to the ELECTRODE terminal of the welder. Connect the work cable to the WORK terminal of the welder.

NOTE: Welding cable must be sized for current and duty cycle of application.

NOTE: Figure C.6 shows the electrode connected for positive polarity. Use the Polarity switch on the Ranger 300 DLX to select the desired electrode polarity.

3.Connect the K691-10 Input Cable as shown in Figure C.6.

4.Set the slide switch on the SG Control Module to the “Lincoln” position.

CAUTION

Be sure the switch is set to the “Lincoln” (contact clo- sure) position before attempting to operate the SG Control Module. Incorrect switch position could result in damage to the SG Control Module and/or the Ranger 300 DLX.

5. Place the IDLER switch in the “HIGH” position.

CAUTION

Any increase of the high idle engine RPM by changing the governor setting or overriding the throttle linkage will cause an increase in the AC auxiliary voltage. If this voltage goes over 140 volts, wire feeder control circuits may be damaged. The engine governor set- ting is preset at the factory - do not adjust above RPM specifications listed in this manual.

6.Set the LOCAL/REMOTE switch to “REMOTE” if a K857 remote control is used. Set the switch to “LOCAL” if no remote control is used.

7.Set the OUTPUT RANGE switch to “WIRE WELD- ING CV.”

8.Set the WELDING TERMINALS switch to “WELD-

ING TERMINALS REMOTELY CONTROLLED.”

9.Adjust wire feed speed at the SG Control Module.

NOTE: For remote control, a K857 remote control is required. Connect it to the 6-pin amphenol.

to Section TOC

to Master TOC

FIGURE C.6

RANGER 300 DLX/K691/K488/K487 SPOOL GUN CONNECTION DIAGRAM

Return

115V RECEPTACLE

RANGER

14 PIN WIRE FEEDER RECEPTACLE

TO WORK

ELECTRODE

K488 SG

CONTROL MODULE

K487-25

SPOOL GUN

6 PIN REMOTE

K691-10

RECEPTACLE

INPUT CABLE

Return to Section TOC

Return to Master TOC

ELECTRODE CABLE

TO WORK TO CONTROL MODULE

RANGER 300 D AND 300 DLX

Page 43
Image 43
Lincoln Electric SVM148-B service manual Return