Power, Battery, & Ground Wiring |
|
|
|
| ||
Power Wiring |
|
|
|
|
| |
✦ NOTE: DO NOT APPLY POWER UNTIL THE INSTALLATION IS |
|
|
|
|
| |
COMPLETE.TURN MASTER POWER SWITCH OFF BEFORE |
|
|
|
|
| |
WIRING. | POWER |
|
| |||
1. Route two wires between the |
|
| ||||
TERMINALS |
| |||||
• For power wire runs up to 75 feet, use 18 AWG, THHN |
| |||||
DC | DC | AC2 | AC1 | EARTH | ||
insulated wire. | ||||||
|
|
|
|
| ||
• For power wire runs up to 150 feet, use 16 AWG, THHN |
|
|
|
| GROUND | |
insulated wire. |
|
|
|
| ||
|
|
|
| STUD | ||
2. Connect the wires to the transformer. Connect the other end of the |
|
|
|
| ||
|
|
|
|
| ||
wires to the |
|
|
|
|
| |
Backup Battery / Uninterruptable Power Supply |
|
|
|
| EARTH | |
Use of battery backup is optional. It will allow the |
|
|
|
| ||
|
|
|
| GROUND | ||
short periods of time without AC power. The door or gate access device |
|
|
|
| ||
|
|
|
| STAKE | ||
must use some type of battery backup of its own for the entire system to | 12 VOLT |
|
|
| ||
|
|
|
| |||
be functional. | BATTERY |
|
|
|
| |
A backup battery will not fi t into the | NOTE: THE OPTIONAL |
|
|
|
| |
battery inside a |
|
|
|
| ||
BACKUP BATTERY |
|
|
|
| ||
✦ NOTE: A backup battery is not required to maintain the |
|
|
|
| ||
WILL REQUIRE AN |
|
|
|
| ||
clock/calendar and programming memory during power outages. |
|
|
|
| ||
EXTERNAL CHARGER |
|
|
|
| ||
1. Route two wires between the |
|
|
|
| ||
|
|
|
|
| ||
2. Connect the Battery positive to the |
|
|
|
| 16 VAC | |
negative to the DC- terminal. |
|
|
|
| ||
|
|
|
| 50 VA | ||
✦ NOTE: The |
|
|
|
| TRANSFORMER | |
An external battery charger will be required to maintain the battery. |
|
|
|
|
| |
Earth Ground |
|
|
|
|
| |
For the best ground, use size 12 gauge solid wire or larger to connect to |
|
|
|
|
| |
an |
|
|
|
|
| |
Telephone company rods and bond the rods together with a new clamp. |
|
|
|
|
| |
Do not disturb the clamps installed by the Power or Telephone Company. |
|
|
|
|
| |
Alternately, connect to a metallic cold water pipe for the earth ground. |
|
|
|
|
| |
1. Connect the wire from the earth ground to the |
|
|
|
|
| |
GROUND STUD. |
|
|
|
|
| |
|
|
|
|
|
| |
A modular connector is provided for the |
|
|
|
|
| |
port.The |
|
|
|
| ||
port. System programming can be performed locally with a computer |
|
|
|
| ||
connected to the |
|
|
|
|
|
COMPUTER'S
COM PORT
SET COMPUTER COM PORT
LINEAR MODEL A2C BAUD RATE TO 38,400 BPS
SERIAL COMPUTER CABLE
NOTE: USE A
11