Linear AE1000Plus Relay Output Wiring, Door or Pedestrian Gate Control, Request-to-ExitInputs

Models: AE1000Plus

1 24
Download 24 pages 33.31 Kb
Page 10
Image 10
Relay Output Wiring

Relay Output Wiring

Any of the four relay outputs channels (A-D) can be used to control access devices on doors or gates.

Door or Pedestrian Gate Control

1.

Install a low voltage electric door strike or magnetic lock as a

 

locking device for the door or pedestrian gate.

2.

Install the power supply or transformer for the locking device. DO

 

NOT POWER THE AE1000Plus FROM THIS POWER SUPPLY.

3.

Connect one wire from the power supply to one wire from the

 

locking device.

TYPICAL DOOR STRIKE HOOKUP

ELECTRIC

DOOR

STRIKE

DOOR

STRIKE

POWER SUPPLY

RELAY

TERMINALS

N.C.

COM

N.O.

DS

GND

RTE

4. Route two wires between the locking device and the AE1000Plus.

Connect one wire to the remaining wire of the locking device.

Connect the other wire to the remaining wire of the power supply.

5A. For a door strike, connect the wires to the AE1000Plus relay COM & N.O. terminals.

5B. For a magnetic lock, connect the wires to the AE1000Plus relay COM & N.C. terminals.

Gate Control

1.Route two wires between the gate and the AE1000Plus.

2.Connect the gate operator’s OPEN terminals to the AE1000Plus relay COM & N.O. terminals.

NOTE: For operator wiring specifics, refer to the gate operator’s wiring diagram.

Request-to-Exit Inputs

Each of the four relay outputs has a request-to-exit input terminal. Grounding this terminal will activate the associated relay. Exit request inputs are typically used with push bars, loop sensors, or pushbuttons.

TYPICAL MAGNETIC LOCK HOOKUP

MAGNETIC

N.C.

DOOR

COM

LOCK

N.O.

 

DOOR

DS

LOCK

GND

POWER SUPPLY

RTE

TYPICAL AUTOMATIC GATE HOOKUP

OPERATOR OPEN

N.C.

N.O.

GATE

COM

 

DS

RELAY RATING:

GND

3 AMPS @ 30 VOLTS

RTE

AC/DC MAXIMUM

 

1.Install the pushbutton or device to signal an exit request.

2.Route two wires from the device to the AE1000Plus.

3.Connect the device’s normally open output to the wires.

4.To activate a relay channel, connect the wires to the associated relay request-to-exit terminal (RTE-A,RTE-B,RTE-C,or RTE-D) and GND terminals.

Sensing Inputs

The sensing inputs can connect to a door switch that monitors whether the controlled door is open or closed.

1.To use the door sense feature to detect forced entry or door ajar conditions, install a normally closed door switch on the door

or pedestrian gate and route two wires from the switch to the AE1000Plus.

2.Connect the sensing device wires to the associated relay sensing terminal (DS-A,DS-B,DS-C,or DS-D) and GND terminals.

NOTE: DOOR SENSE CONTACT

IS NORMALLY CLOSED

DOOR

SENSE

CONTACT

DOOR EXIT

REQUEST

BUTTON

OR

GATE

EXIT LOOP

SENSOR

N.C.

COM

N.O.

DS

GND

RTE

RELAY

TERMINALS

DS = SENSING INPUT

RTE = REQUEST-TO-EXIT

NOTE: DOOR EXIT REQUEST BUTTON AND GATE EXIT LOOP CONTACT ARE NORMALLY OPEN

10