Linear AE1000Plus RS-485Network Wiring, Network Wiring with Hub, Network “Daisy-chain”Wiring

Models: AE1000Plus

1 24
Download 24 pages 33.31 Kb
Page 17
Image 17
RS-485 Network Wiring

Optional Network Connections (Continued)

RS-485 Network Wiring

Network wiring conforms to 3-wire RS-485 electrical specifi cations. Units connected in the network can be wired using one unit as a “hub” or by wiring from one unit to the next in “daisy-chain” fashion. See the fi gures for wiring options.

Use Belden 9925 or Carol C0600 shielded cable or equivalent. Maximum wire run distance is 4000 feet.

NOTE: Be sure to connect the cable’s shield to one of the GND terminals.

Network Wiring with Hub

1.Mount and install the units for the network.

2.Choose one unit to be the Network Hub. Usually this would be a centrally located or “master” unit.

3.Route 3-conductor shielded cable from the hub unit to one of the other units. Repeat this step to connect the hub unit to each of the other units.

4.Connect the 3-conductor cable to each unit’s NETWORK terminals.

ACCESS CONTROL HOMERUN NETWORK USING ONE UNIT AS A NETWORK MASTER

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NETWORK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MASTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT "1"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

NET-B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NET-A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CABLE SHIELDS

 

 

 

 

 

 

 

 

 

 

 

 

 

ONLY AT ONE END

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NETWORK

UNIT "2"

NET-B

GND

NET-A

NETWORK

UNIT "3"

NET-B

GND

NET-A

NETWORK

UNIT "4"

NET-B

GND

NET-A

Network “Daisy-chain” Wiring

1.Mount and install the units for the network.

2.Route 3-conductor shielded cable from one unit to the next unit until there is cabling run to all of the units.

3.Connect the 3-conductor cable to each unit’s NETWORK terminals.

NETWORK

 

NETWORK

MASTER

 

SHIELD

UNIT "2"

UNIT "1"

 

NET-B

NET-B

GND

GND

NET-A

NET-A

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NETWORK

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT "3"

 

 

 

 

 

 

 

 

 

 

 

 

 

ACCESS CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

NET-B

 

 

 

 

 

 

 

 

 

 

 

 

NETWORK USING

 

 

 

 

 

 

 

 

 

 

 

 

"DAISY CHAIN"

 

 

 

 

 

 

 

 

 

 

 

 

GND

WIRING

 

 

 

 

 

 

 

 

 

 

 

 

NET-A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NETWORK

 

 

 

 

 

 

 

 

 

 

 

UNIT "4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NET-B

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CABLE SHIELDS

 

 

 

 

 

 

 

 

 

GND

ONLY AT ONE END

 

 

 

 

 

 

 

 

 

NET-A

 

 

 

 

 

 

17

Page 17
Image 17
Linear AE1000Plus installation instructions RS-485Network Wiring, Network Wiring with Hub, Network “Daisy-chain”Wiring