Wiegand Accessories
The two AM3Plus Wiegand inputs (READER A & B) can connect to a large variety of 26, 30, and
✦NOTE: Depending on the Wiegand accessory used, the LED1, LED2, and HOLD connections may not be required.
•LED1 output is switched to ground during
•LED2 output is switched to ground for one second during access time.
1.Mount and install the Wiegand accessory as described in its installation instructions.
2.Route a cable from the AM3Plus to the accessory.
•For wire runs up to 300 feet use 24 AWG Belden 9931 or equivalent.
•For wire runs up to 500 feet use 20 AWG Weico 9405 or equivalent.
3.Connect the cable to the accessory and the AM3Plus as shown in the fi gure.
AM3PLUS | PWR GND DAT0 DAT1 LED1 HOLD LED2 |
| |
READER |
|
TERMINALS |
|
PWR GND | DAT0 DAT1 LED1 | HOLD | LED2 |
| REMOTE |
|
|
| WIEGAND |
|
|
| DEVICE |
|
|
NOTE: THE LED1, LED2, AND HOLD CONNECTIONS MAY NOT BE REQUIRED DEPENDING ON THE WIEGAND DEVICE USED
RS-232 Port
A modular connector is provided for the
AM3PLUS
COMPUTER'S
COM PORT
SET COMPUTER COM PORT
LINEAR MODEL A2C BAUD RATE TO 38,400 BPS SERIAL COMPUTER CABLE
NOTE: USE A
12