Optional Network Connections (Continued)

RS-485 Network Wiring

Network wiring conforms to 3-wire RS-485 electrical specifi cations. Units connected in the network can be wired using one unit as a “hub” or by wiring from one unit to the next in “daisy-chain” fashion. See the fi gures for wiring options.

Use Belden 9925 or Carol C0600 shielded cable or equivalent. Maximum wire run distance is 4000 feet.

NOTE: Be sure to connect the cable’s shield to one of the GND terminals.

Network Wiring with Hub

1.Mount and install the units for the network.

2.Choose one unit to be the Network Hub. Usually this would be a centrally located or “master” unit.

3.Route 3-conductor shielded cable from the hub unit to one of the other units. Repeat this step to connect the hub unit to each of the other units.

4.Connect the 3-conductor cable to each unit’s NETWORK terminals.

ACCESS CONTROL HOMERUN NETWORK

 

USING ONE UNIT AS A NETWORK MASTER

NETWORK

 

 

 

SHIELD

UNIT "2"

 

 

 

 

NET-B

 

 

GND

 

 

NET-A

NETWORK

 

NETWORK

MASTER

 

 

UNIT "3"

UNIT "1"

SHIELD

 

NET-B

 

NET-B

GND

 

GND

NET-A

 

NET-A

 

NOTE: GROUND

 

 

CABLE SHIELDS

 

 

ONLY AT ONE END

NETWORK

 

SHIELD

UNIT "4"

 

 

 

 

NET-B

 

 

GND

 

 

NET-A

Network “Daisy-chain” Wiring

1.Mount and install the units for the network.

2.Route 3-conductor shielded cable from one unit to the next unit until there is cabling run to all of the units.

3.Connect the 3-conductor cable to each unit’s NETWORK terminals.

NETWORK

 

NETWORK

MASTER

 

SHIELD

UNIT "2"

UNIT "1"

 

NET-B

NET-B

GND

GND

NET-A

NET-A

SHIELD

NETWORK

 

UNIT "3"

ACCESS CONTROL

NET-B

NETWORK USING

GND

"DAISY CHAIN"

NET-A

WIRING

SHIELD

NETWORK

 

UNIT "4"

NOTE: GROUND

NET-B

CABLE SHIELDS

GND

ONLY AT ONE END

NET-A

15

Page 15
Image 15
Linear AM3Plus installation instructions RS-485 Network Wiring, Network Wiring with Hub, Network Daisy-chain Wiring