Power Requirements

Table 3 Power Requirements

Unit/Component

 

 

Requirements

 

 

 

 

 

 

 

Domestic

 

International

 

 

 

AC Power

250 VAC, 30 A

230 VAC, 32 A

 

 

 

AC Plug

NEMA L6-30P, locking plug

IEC 309 locking plug

 

 

 

Receptacle

6-30R, receptacle

IEC 309 receptacle

 

 

 

 

 

 

Circuit Breaker

 

 

20 A

 

 

 

 

 

 

Voltage Range

 

 

180 to 257 VAC

 

 

 

 

 

 

Frequency

 

 

49 to 50.5 Hz or 59 to 60.6 Hz

 

 

 

 

 

 

 

Current

 

 

220 VAC, 50/60 Hz

 

(specified frequency)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuration A1

Configuration B1

Configuration C1

Operational Current

LP Drives2

 

7.35 A

14.70 A

13.16 A

HH Drives2

 

7.70 A

15.40 A

13.72 A

 

 

Surge Current

LP Drives

 

10.95 A

21.90 A

22.20 A

 

 

 

 

 

HH Drives

 

11.45 A

22.90 A

23.00 A

 

 

 

 

 

 

 

 

1Power specifications for three configurations containing Low-Profile (LP) and Half-Height (HH) drives, including: Configuration A contains 1 command module and 5 drive modules

Configuration B contains 2 command modules and 10 drive modules Configuration C contains 3 command modules and 8 drive modules

2LP drives are 1.0 inch tall; HH drives are 1.6 inches tall.